GE Multilin
B90 Low Impedance Bus Differential System
5-129
5 SETTINGS
5.5 GROUPED ELEMENTS
5
0.5
8.090
3.514
1.471
0.899
0.654
0.526
0.450
0.401
0.368
0.345
1.0
16.179
7.028
2.942
1.798
1.308
1.051
0.900
0.802
0.736
0.689
2.0
32.358
14.055
5.885
3.597
2.616
2.103
1.799
1.605
1.472
1.378
4.0
64.716
28.111
11.769
7.193
5.232
4.205
3.598
3.209
2.945
2.756
6.0
97.074
42.166
17.654
10.790
7.849
6.308
5.397
4.814
4.417
4.134
8.0
129.432
56.221
23.538
14.387
10.465
8.410
7.196
6.418
5.889
5.513
10.0
161.790
70.277
29.423
17.983
13.081
10.513
8.995
8.023
7.361
6.891
IEEE MODERATELY INVERSE
0.5
3.220
1.902
1.216
0.973
0.844
0.763
0.706
0.663
0.630
0.603
1.0
6.439
3.803
2.432
1.946
1.688
1.526
1.412
1.327
1.260
1.207
2.0
12.878
7.606
4.864
3.892
3.377
3.051
2.823
2.653
2.521
2.414
4.0
25.756
15.213
9.729
7.783
6.753
6.102
5.647
5.307
5.041
4.827
6.0
38.634
22.819
14.593
11.675
10.130
9.153
8.470
7.960
7.562
7.241
8.0
51.512
30.426
19.458
15.567
13.507
12.204
11.294
10.614
10.083
9.654
10.0
64.390
38.032
24.322
19.458
16.883
15.255
14.117
13.267
12.604
12.068
Table 5–18: IEEE CURVE TRIP TIMES (IN SECONDS)
MULTIPLIER
(TDM)
CURRENT (
I
/
I
pickup
)
1.5
2.0
3.0
4.0
5.0
6.0
7.0
8.0
9.0
10.0
Summary of Contents for B90
Page 10: ...x B90 Low Impedance Bus Differential System GE Multilin TABLE OF CONTENTS ...
Page 284: ...5 166 B90 Low Impedance Bus Differential System GE Multilin 5 8 TESTING 5 SETTINGS 5 ...
Page 334: ...10 8 B90 Low Impedance Bus Differential System GE Multilin 10 2 BATTERIES 10 MAINTENANCE 10 ...
Page 338: ...A 4 B90 Low Impedance Bus Differential System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Page 460: ...C 30 B90 Low Impedance Bus Differential System GE Multilin C 7 LOGICAL NODES APPENDIX C C ...
Page 476: ...E 10 B90 Low Impedance Bus Differential System GE Multilin E 1 IEC 60870 5 104 APPENDIX E E ...
Page 502: ...viii B90 Low Impedance Bus Differential System GE Multilin INDEX ...