GE Multilin
B90 Low Impedance Bus Differential System
7-3
7 COMMANDS AND TARGETS
7.1 COMMANDS
7
7.1.5 RELAY MAINTENANCE
PATH: COMMANDS
RELAY MAINTENANCE
This menu contains commands for relay maintenance purposes. Commands for the lamp test and order code are activated
by changing a command setting to “Yes” and pressing the ENTER key. The command setting will then automatically revert
to “No”. The service command is activated by entering a numerical code and pressing the ENTER key.
The
PERFORM LAMPTEST
command turns on all faceplate LEDs and display pixels for a short duration. The
UPDATE
ORDER CODE
command causes the relay to scan the backplane for the hardware modules and update the order code to
match. If an update occurs, the following message is shown.
There is no impact if there have been no changes to the hardware modules. When an update does not occur, the
ORDER
CODE NOT UPDATED
message will be shown.
The
REBOOT RELAY COMMAND
reboots the relay so that changes to configuration settings can take effect. In most cases, if
changes are made to the configuration settings these changes do not take effect unless the relay is rebooted.
With the CyberSentry option, the Administrator or Operator role can initiate the Reboot Relay command.
The
SERVICE COMMAND
is used to perform specific B90 service actions. Presently, there is only one service action avail-
able. Code “101” is used to clear factory diagnostic information stored in the non-volatile memory. If a code other than “101”
is entered, the command will be ignored and no actions will be taken. Various self-checking diagnostics are performed in
the background while the B90 is running, and diagnostic information is stored on the non-volatile memory from time to time
based on the self-checking result. Although the diagnostic information is cleared before the B90 is shipped from the factory,
the user may want to clear the diagnostic information for themselves under certain circumstances. For example, it may be
desirable to clear diagnostic information after replacement of hardware. Once the diagnostic information is cleared, all self-
checking variables are reset to their initial state and diagnostics will restart from scratch.
SAVE VOLATILE DATA
saves this data to compact flash memory prior to shutdown. This allows the saved data to be as recent
as possible instead of relying on the periodic timer to save the data.
COMMANDS
RELAY MAINTENANCE
PERFORM LAMPTEST?
No
Range: No, Yes
UPDATE ORDER CODE?
No
Range: No, Yes
REBOOT RELAY?
No
Range: No, Yes
SERVICE COMMAND:
0
Range: 0, 101
SAVE VOLATILE DATA?
No
Range: No, Yes
UPDATING...
PLEASE WAIT
NOTE
Summary of Contents for B90
Page 10: ...x B90 Low Impedance Bus Differential System GE Multilin TABLE OF CONTENTS ...
Page 284: ...5 166 B90 Low Impedance Bus Differential System GE Multilin 5 8 TESTING 5 SETTINGS 5 ...
Page 334: ...10 8 B90 Low Impedance Bus Differential System GE Multilin 10 2 BATTERIES 10 MAINTENANCE 10 ...
Page 338: ...A 4 B90 Low Impedance Bus Differential System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Page 460: ...C 30 B90 Low Impedance Bus Differential System GE Multilin C 7 LOGICAL NODES APPENDIX C C ...
Page 476: ...E 10 B90 Low Impedance Bus Differential System GE Multilin E 1 IEC 60870 5 104 APPENDIX E E ...
Page 502: ...viii B90 Low Impedance Bus Differential System GE Multilin INDEX ...