7-6
B90 Low Impedance Bus Differential System
GE Multilin
7.2 TARGETS
7 COMMANDS AND TARGETS
7
•
A
RELAY OUT OF SERVICE
event is recorded.
b) MAJOR SELF-TEST ERROR MESSAGES
The major self-test errors are outlined in this section.
•
Latched target message
: Yes.
•
Description of problem
: Module hardware failure detected.
•
How often the test is performed
: Module dependent.
•
What to do
: Contact the factory and supply the failure code noted in the display. The “xxx” text identifies the failed mod-
ule (for example, F8L).
•
Latched target message
: Yes.
•
Description of problem
: One or more installed hardware modules is not compatible with the B90 order code.
•
How often the test is performed
: Module dependent.
•
What to do
: Contact the factory and supply the failure code noted in the display. The “xxx” text identifies the failed mod-
ule (for example, F8L).
•
Latched target message
: No.
•
Description of problem
: The configuration of modules does not match the order code stored in the B90.
•
How often the test is performed
: On power up. Afterwards, the backplane is checked for missing cards every five sec-
onds.
•
What to do
: Check all modules against the order code, ensure they are inserted properly, and cycle control power. If
the problem persists, contact the factory.
•
Latched target message
: No.
•
Description of problem
: A FlexLogic equation is incorrect.
•
How often the test is performed
: The test is event driven, performed whenever FlexLogic equations are modified
.
•
What to do
: Finish all equation editing and use self tests to debug any errors.
•
Latched target message
: No.
•
Description of problem
: The
PRODUCT SETUP
INSTALLATION
RELAY SETTINGS
setting indicates the B90 is not pro-
grammed.
•
How often the test is performed
: On power up and whenever the
PRODUCT SETUP
INSTALLATION
RELAY SETTINGS
setting is altered
.
•
What to do
: Program all settings and then set
PRODUCT SETUP
INSTALLATION
RELAY SETTINGS
to “Programmed”.
MODULE FAILURE___:
Contact Factory (xxx)
INCOMPATIBLE H/W:
Contact Factory (xxx)
EQUIPMENT MISMATCH:
with 2nd line detail
FLEXLOGIC ERROR:
with 2nd line detail
UNIT NOT PROGRAMMED:
Check Settings
Summary of Contents for B90
Page 10: ...x B90 Low Impedance Bus Differential System GE Multilin TABLE OF CONTENTS ...
Page 284: ...5 166 B90 Low Impedance Bus Differential System GE Multilin 5 8 TESTING 5 SETTINGS 5 ...
Page 334: ...10 8 B90 Low Impedance Bus Differential System GE Multilin 10 2 BATTERIES 10 MAINTENANCE 10 ...
Page 338: ...A 4 B90 Low Impedance Bus Differential System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Page 460: ...C 30 B90 Low Impedance Bus Differential System GE Multilin C 7 LOGICAL NODES APPENDIX C C ...
Page 476: ...E 10 B90 Low Impedance Bus Differential System GE Multilin E 1 IEC 60870 5 104 APPENDIX E E ...
Page 502: ...viii B90 Low Impedance Bus Differential System GE Multilin INDEX ...