B-20
B90 Low Impedance Bus Differential System
GE Multilin
B.4 MEMORY MAPPING
APPENDIX B
B
40A9
DNP Unsolicited Responses Function
0 to 1
---
1
F102
0 (Disabled)
40AA
DNP Unsolicited Responses Timeout
0 to 60
s
1
F001
5
40AB
DNP Unsolicited Responses Maximum Retries
1 to 255
---
1
F001
10
40AC
DNP Unsolicited Responses Destination Address
0 to 65519
---
1
F001
1
40AD
Ethernet Operation Mode
0 to 1
---
1
F192
1 (Half-Duplex)
40AE
DNP Current Scale Factor
0 to 8
---
1
F194
2 (1)
40AF
DNP Voltage Scale Factor
0 to 8
---
1
F194
2 (1)
40B0
DNP Power Scale Factor
0 to 8
---
1
F194
2 (1)
40B1
DNP Energy Scale Factor
0 to 8
---
1
F194
2 (1)
40B2
DNP Power Scale Factor
0 to 8
---
1
F194
2 (1)
40B3
DNP Other Scale Factor
0 to 8
---
1
F194
2 (1)
40B4
DNP Current Default Deadband
0 to 100000000
---
1
F003
30000
40B6
DNP Voltage Default Deadband
0 to 100000000
---
1
F003
30000
40B8
DNP Power Default Deadband
0 to 100000000
---
1
F003
30000
40BA
DNP Energy Default Deadband
0 to 100000000
---
1
F003
30000
40BC
DNP Power Factor Default Deadband
0 to 100000000
--
1
F003
30000
40BE
DNP Other Default Deadband
0 to 100000000
---
1
F003
30000
40C0
DNP IIN Time Synchronization Bit Period
1 to 10080
min
1
F001
1440
40C1
DNP Message Fragment Size
30 to 2048
---
1
F001
240
40C2
DNP Client Address 3
0 to 4294967295
---
1
F003
0
40C4
DNP Client Address 4
0 to 4294967295
---
1
F003
0
40C6
DNP Client Address 5
0 to 4294967295
---
1
F003
0
40C8
DNP Number of Paired Binary Output Control Points
0 to 32
---
1
F001
0
40C9
DNP TCP Connection Timeout
10 to 65535
---
1
F001
120
40CA
DNP Communications Reserved (22 items)
0 to 1
---
1
F001
0
40E0
TCP Port Number for the IEC 60870-5-104 Protocol
0 to 65535
---
1
F001
2404
40E1
IEC 60870-5-104 Protocol Function
0 to 1
---
1
F102
0 (Disabled)
40E2
IEC 60870-5-104 Protocol Common Address of ASDU
0 to 65535
---
1
F001
0
40E3
IEC 60870-5-104 Protocol Cyclic data Transmit Period
1 to 65535
s
1
F001
60
40E4
IEC 60870-5-104 Current Default Threshold
0 to 100000000
---
1
F003
30000
40E6
IEC 60870-5-104 Voltage Default Threshold
0 to 100000000
---
1
F003
30000
40E8
IEC 60870-5-104 Power Default Threshold
0 to 100000000
---
1
F003
30000
40EA
IEC 60870-5-104 Energy Default Threshold
0 to 100000000
---
1
F003
30000
40EC
IEC 60870-5-104 Power Default Threshold
0 to1
---
0.01
F001
100
40EE
IEC 60870-5-104 Other Default Threshold
0 to 100000000
---
1
F003
30000
40F0
IEC 60870-5-104 Client Address (5 items)
0 to 4294967295
---
1
F003
0
4104
IEC 60870-5-104 Redundancy Port
0 to 1
---
1
F126
0 (No)
4105
Port 2 IP Address
0 to 4294967295
---
1
F003
56554706
4107
Port 2 IP Subnet Mask
0 to 4294967295
---
1
F003
4294966272
4109
Port 2 Gateway IP Address
0 to 4294967295
---
1
F003
56554497
410B
PRT2 Ethernet Operation Mode
0 to 1
---
1
F192
1 (Full-Duplex)
410C
PRT2 Redundancy Enabled
0 to 2
---
1
F627
0 (None)
410D
Port 3 IP Address
0 to 4294967295
---
1
F003
56554706
410F
Port 3 IP Subnet Mask
0 to 4294967295
---
1
F003
4294966272
4111
Port 3 Gateway IP Address
0 to 4294967295
---
1
F003
56554497
4113
Port 3 Ethernet Operation Mode
0 to 1
---
1
F192
1 (Full-Duplex)
4114
PRT1 GOOSE Enabled
0 to 1
---
1
F102
1 (Enabled)
4115
PRT2 GOOSE Enabled
0 to 1
---
1
F102
1 (Enabled)
4116
PRT3 GOOSE Enabled
0 to 1
---
1
F102
1 (Enabled)
4119
PRT2 PRP Mcst Addr
---
---
---
F072
0
411C
IEC Communications Reserved (33 items)
0 to 1
---
1
F001
0
413E
High Enet Traffic Function
0 to 1
---
1
F102
0 (Disabled)
413F
High Enet Traffic Events
0 to 1
---
1
F102
0 (Disabled)
4140
DNP Object 1 Default Variation
1 to 2
---
1
F001
2
Table B–10: MODBUS MEMORY MAP (Sheet 12 of 52)
ADDR
REGISTER NAME
RANGE
UNITS
STEP
FORMAT
DEFAULT
Summary of Contents for B90
Page 10: ...x B90 Low Impedance Bus Differential System GE Multilin TABLE OF CONTENTS ...
Page 284: ...5 166 B90 Low Impedance Bus Differential System GE Multilin 5 8 TESTING 5 SETTINGS 5 ...
Page 334: ...10 8 B90 Low Impedance Bus Differential System GE Multilin 10 2 BATTERIES 10 MAINTENANCE 10 ...
Page 338: ...A 4 B90 Low Impedance Bus Differential System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Page 460: ...C 30 B90 Low Impedance Bus Differential System GE Multilin C 7 LOGICAL NODES APPENDIX C C ...
Page 476: ...E 10 B90 Low Impedance Bus Differential System GE Multilin E 1 IEC 60870 5 104 APPENDIX E E ...
Page 502: ...viii B90 Low Impedance Bus Differential System GE Multilin INDEX ...