GE Multilin
L30 Line Current Differential System
4-17
4 HUMAN INTERFACES
4.3 FACEPLATE INTERFACE
4
•
GROUP 1...6
: The illuminated GROUP is the active settings group.
•
BREAKER 1(2) OPEN
: The breaker is open.
•
BREAKER 1(2) CLOSED
: The breaker is closed.
•
BREAKER 1(2) TROUBLE
: A problem related to the breaker has been detected.
•
SYNCHROCHECK NO1(2) IN-SYNCH
: Voltages have satisfied the synchrocheck element.
•
RECLOSE ENABLED
: The recloser is operational.
•
RECLOSE DISABLED
: The recloser is not operational.
•
RECLOSE IN PROGRESS
: A reclose operation is in progress.
•
RECLOSE LOCKED OUT
: The recloser is not operational and requires a reset.
The relay is shipped with the default label for the LED panel 2. The LEDs, however, are not pre-programmed. To match the
pre-printed label, the LED settings must be entered as shown in the
User-programmable LEDs
section of chapter 5. The
LEDs are fully user-programmable. The default labels can be replaced by user-printed labels for both panels as explained
in the following section.
Figure 4–21: LED PANEL 2 (DEFAULT LABELS)
4.3.3 CUSTOM LABELING OF LEDS
a) ENHANCED FACEPLATE
The following procedure requires these pre-requisites:
•
EnerVista UR Setup software is installed and operational
•
The L30 settings have been saved to a settings file
•
The L30 front panel label cutout sheet (GE Multilin part number 1006-0047) has been downloaded from
www.gedigitalenergy.com/products/support/ur/URLEDenhanced.doc
and printed
•
Small-bladed knife
To create custom LED labels for the enhanced front panel display:
1.
Start the EnerVista UR Setup software.
842784A1.CDR
Summary of Contents for L30
Page 10: ...x L30 Line Current Differential System GE Multilin TABLE OF CONTENTS ...
Page 30: ...1 20 L30 Line Current Differential System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Page 370: ...5 244 L30 Line Current Differential System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Page 464: ...A 10 L30 Line Current Differential System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Page 600: ...C 30 L30 Line Current Differential System GE Multilin C 7 LOGICAL NODES APPENDIX C C ...
Page 610: ...D 10 L30 Line Current Differential System GE Multilin D 1 IEC 60870 5 104 APPENDIX D D ...
Page 622: ...E 12 L30 Line Current Differential System GE Multilin E 2 DNP POINT LISTS APPENDIX E E ...
Page 634: ...F 12 L30 Line Current Differential System GE Multilin F 3 WARRANTY APPENDIX F F ...
Page 644: ...x L30 Line Current Differential System GE Multilin INDEX ...