GE Multilin
L30 Line Current Differential System
5-29
5 SETTINGS
5.2 PRODUCT SETUP
5
The DNP / IEC 60870-5-104 point lists always begin with point 0 and end at the first “Off” value. Since DNP / IEC
60870-5-104 point lists must be in one continuous block, any points assigned after the first “Off” point are ignored.
Changes to the DNP / IEC 60870-5-104 point lists will not take effect until the L30 is restarted.
h) IEC 61850 PROTOCOL
PATH: SETTINGS
PRODUCT SETUP
COMMUNICATIONS
IEC 61850 PROTOCOL
The L30 Line Current Differential System is provided with optional IEC 61850 communications capability.
This feature is specified as a software option at the time of ordering. Refer to the
Ordering
section of chap-
ter 2 for additional details.
Use independent ports for IEC 61850 communication and take care when configuring the settings,
else loss of protection or misoperation of the relay can result.
The L30 supports the Manufacturing Message Specification (MMS) protocol as specified by IEC 61850. MMS is supported
over two protocol stacks: TCP/IP over ethernet and TP4/CLNP (OSI) over ethernet. The L30 operates as an IEC 61850
server. The
Remote inputs and outputs
section in this chapter describe the peer-to-peer GSSE/GOOSE message scheme.
The GSSE/GOOSE configuration main menu is divided into two areas: transmission and reception.
PATH: SETTINGS
PRODUCT SETUP
COMMUNICATIONS
IEC 61850 PROTOCOL
GSSE/GOOSE CONFIGURATION
IEC 61850 PROTOCOL
GSSE / GOOSE
CONFIGURATION
MESSAGE
SERVER
CONFIGURATION
MESSAGE
IEC 61850 LOGICAL
NODE NAME PREFIXES
MESSAGE
MMXU DEADBANDS
MESSAGE
GGIO1 STATUS
CONFIGURATION
MESSAGE
GGIO2 CONTROL
CONFIGURATION
MESSAGE
GGIO4 ANALOG
CONFIGURATION
MESSAGE
GGIO5 UINTEGER
CONFIGURATION
MESSAGE
REPORT CONTROL
CONFIGURATION
MESSAGE
XCBR
CONFIGURATION
MESSAGE
XSWI
CONFIGURATION
GSSE / GOOSE
CONFIGURATION
TRANSMISSION
MESSAGE
RECEPTION
NOTE
NOTE
Summary of Contents for L30
Page 10: ...x L30 Line Current Differential System GE Multilin TABLE OF CONTENTS ...
Page 30: ...1 20 L30 Line Current Differential System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Page 370: ...5 244 L30 Line Current Differential System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Page 464: ...A 10 L30 Line Current Differential System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Page 600: ...C 30 L30 Line Current Differential System GE Multilin C 7 LOGICAL NODES APPENDIX C C ...
Page 610: ...D 10 L30 Line Current Differential System GE Multilin D 1 IEC 60870 5 104 APPENDIX D D ...
Page 622: ...E 12 L30 Line Current Differential System GE Multilin E 2 DNP POINT LISTS APPENDIX E E ...
Page 634: ...F 12 L30 Line Current Differential System GE Multilin F 3 WARRANTY APPENDIX F F ...
Page 644: ...x L30 Line Current Differential System GE Multilin INDEX ...