7-12
L30 Line Current Differential System
GE Multilin
7.2 TARGETS
7 COMMANDS AND TARGETS
7
To further isolate AC input discrepancy errors, put the relay in test-isolated mode, then one by one, temporally change an
AC bank crosschecking setting to none, until the Process Bus Failure clears. Once the problem AC bank has been identi-
fied, the values from each of the two Bricks can be examined individually by temporarily mapping each to an AC bank with
a single origin.
Process Bus Trouble Minor Self-Test
Description: Communications problems with one or more Bricks. The text of the message identifies the affected field units.
This self-test is initiated by low received signal levels at either the Brick or Process Card end, and by the sustained failure
to receive poll responses from the proper Brick.
Severity: This self-test error does not directly inhibit protection. However, the affected Brick inputs/outputs may not be avail-
able to the UR-series device.
If this message appears, check the field unit actual values. An indication of equipment mismatch means that messages are
being received from a Brick, but there is a discrepancy between the settings and the actual Brick serial number, order code,
and/or core number. Check that the correct core on the correct Brick is patched through to the correct Process Card port,
and that the field unit settings are correct. An indication of communications loss means that no messages are being
received. Check that the patching is correct, and that the Brick has power. If that is not the problem, use a professional opti-
cal fiber connector cleaning kit to clean both sides of all optical fiber connections from the Process Card through to the
affected Brick. If the problem continues after cleaning, consult the factory.
Brick Trouble Minor Self-Test
Description: Brick internal self-testing has detected a trouble internal to the Brick.
Severity: This self-test error does not directly inhibit protection. However, some or all of the affected Brick inputs/outputs
may not be available to the UR-series device.
If this message appears, check the Brick environment for over/under temperatures and the voltage of its power source. If
the ambient temperature and supply voltage are within Brick specifications, consult the factory. Troubles resulting from a
Brick output failing to respond to an output command can only be detected while the command is active, and so in this case
the target is latched. A latched target can be unlatched by pressing the faceplate reset key if the command has ended,
however the output may still be non-functional.
Summary of Contents for L30
Page 10: ...x L30 Line Current Differential System GE Multilin TABLE OF CONTENTS ...
Page 30: ...1 20 L30 Line Current Differential System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Page 370: ...5 244 L30 Line Current Differential System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Page 464: ...A 10 L30 Line Current Differential System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Page 600: ...C 30 L30 Line Current Differential System GE Multilin C 7 LOGICAL NODES APPENDIX C C ...
Page 610: ...D 10 L30 Line Current Differential System GE Multilin D 1 IEC 60870 5 104 APPENDIX D D ...
Page 622: ...E 12 L30 Line Current Differential System GE Multilin E 2 DNP POINT LISTS APPENDIX E E ...
Page 634: ...F 12 L30 Line Current Differential System GE Multilin F 3 WARRANTY APPENDIX F F ...
Page 644: ...x L30 Line Current Differential System GE Multilin INDEX ...