GE Multilin
L30 Line Current Differential System
9-19
9 THEORY OF OPERATION
9.2 OPERATING CONDITION CHARACTERISTICS
9
Figure 9–8: SETTINGS IMPACT ON RESTRAINT CHARACTERISTIC
831725A1.CDR
0
4
8
12
I
rem pu
OPERATE
RESTRAINT
BP=8, P=2, S1=30%, S2=50%
BP=4, P=1, S1=30%, S2=50%
BP=4, P=1, S1=20%, S2=40%
OPERATE
I
loc pu
16
20
0
4
8
10
16
20