B-18
L30 Line Current Differential System
GE Multilin
B.4 MEMORY MAPPING
APPENDIX B
B
26B3
IEC 61850 GGIO5 uinteger input 4 operand
---
---
---
F612
0
26B4
IEC 61850 GGIO5 uinteger input 5 operand
---
---
---
F612
0
26B5
IEC 61850 GGIO5 uinteger input 6 operand
---
---
---
F612
0
26B6
IEC 61850 GGIO5 uinteger input 7 operand
---
---
---
F612
0
26B7
IEC 61850 GGIO5 uinteger input 8 operand
---
---
---
F612
0
26B8
IEC 61850 GGIO5 uinteger input 9 operand
---
---
---
F612
0
26B9
IEC 61850 GGIO5 uinteger input 10 operand
---
---
---
F612
0
26BA
IEC 61850 GGIO5 uinteger input 11 operand
---
---
---
F612
0
26BB
IEC 61850 GGIO5 uinteger input 12 operand
---
---
---
F612
0
26BC
IEC 61850 GGIO5 uinteger input 13 operand
---
---
---
F612
0
26BD
IEC 61850 GGIO5 uinteger input 14 operand
---
---
---
F612
0
26BE
IEC 61850 GGIO5 uinteger input 15 operand
---
---
---
F612
0
26BF
IEC 61850 GGIO5 uinteger input 16 operand
---
---
---
F612
0
IEC 61850 received integers (read only actual values)
26F0
IEC 61850 received uinteger 1
0 to 4294967295
---
1
F003
0
26F2
IEC 61850 received uinteger 2
0 to 4294967295
---
1
F003
0
26F4
IEC 61850 received uinteger 3
0 to 4294967295
---
1
F003
0
26F6
IEC 61850 received uinteger 4
0 to 4294967295
---
1
F003
0
26F8
IEC 61850 received uinteger 5
0 to 4294967295
---
1
F003
0
26FA
IEC 61850 received uinteger 6
0 to 4294967295
---
1
F003
0
26FC
IEC 61850 received uinteger 7
0 to 4294967295
---
1
F003
0
26FE
IEC 61850 received uinteger 8
0 to 4294967295
---
1
F003
0
2700
IEC 61850 received uinteger 9
0 to 4294967295
---
1
F003
0
2702
IEC 61850 received uinteger 10
0 to 4294967295
---
1
F003
0
2704
IEC 61850 received uinteger 11
0 to 4294967295
---
1
F003
0
2706
IEC 61850 received uinteger 12
0 to 4294967295
---
1
F003
0
2708
IEC 61850 received uinteger 13
0 to 4294967295
---
1
F003
0
270A
IEC 61850 received uinteger 14
0 to 4294967295
---
1
F003
0
270C
IEC 61850 received uinteger 15
0 to 4294967295
---
1
F003
0
270E
IEC 61850 received uinteger 16
0 to 4294967295
---
1
F003
0
Expanded FlexStates (Read Only)
2B00
FlexStates, one per register (256 items)
0 to 1
---
1
F108
0 (Off)
Expanded Digital Input/Output states (Read Only)
2D00
Contact Input States, one per register (96 items)
0 to 1
---
1
F108
0 (Off)
2D80
Contact Output States, one per register (64 items)
0 to 1
---
1
F108
0 (Off)
2E00
Virtual Output States, one per register (96 items)
0 to 1
---
1
F108
0 (Off)
Expanded Remote Input/Output Status (Read Only)
2F00
Remote Device States, one per register (16 items)
0 to 1
---
1
F155
0 (Offline)
2F80
Remote Input States, one per register (64 items)
0 to 1
---
1
F108
0 (Off)
Oscillography Values (Read Only)
3000
Oscillography Number of Triggers
0 to 65535
---
1
F001
0
3001
Oscillography Available Records
0 to 65535
---
1
F001
0
3002
Oscillography Last Cleared Date
0 to 400000000
---
1
F050
0
3004
Oscillography Number Of Cycles Per Record
0 to 65535
---
1
F001
0
Oscillography Commands (Read/Write Command)
3005
Oscillography Force Trigger
0 to 1
---
1
F126
0 (No)
3011
Oscillography Clear Data
0 to 1
---
1
F126
0 (No)
3012
Oscillography Number of Triggers
0 to 32767
---
1
F001
0
Fault Report Indexing (Read Only Non-Volatile)
3020
Number of Fault Reports
0 to 65535
---
1
F001
0
Fault Report Actuals (Read Only Non-Volatile) (15 modules)
3030
Fault Report 1 Time
0 to 4294967295
---
1
F050
0
3032
Fault Report 2 Time
0 to 4294967295
---
1
F050
0
3034
Fault Report 3 Time
0 to 4294967295
---
1
F050
0
Table B–9: MODBUS MEMORY MAP (Sheet 10 of 61)
ADDR
REGISTER NAME
RANGE
UNITS
STEP
FORMAT
DEFAULT
Summary of Contents for L30
Page 10: ...x L30 Line Current Differential System GE Multilin TABLE OF CONTENTS ...
Page 30: ...1 20 L30 Line Current Differential System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Page 370: ...5 244 L30 Line Current Differential System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Page 464: ...A 10 L30 Line Current Differential System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Page 600: ...C 30 L30 Line Current Differential System GE Multilin C 7 LOGICAL NODES APPENDIX C C ...
Page 610: ...D 10 L30 Line Current Differential System GE Multilin D 1 IEC 60870 5 104 APPENDIX D D ...
Page 622: ...E 12 L30 Line Current Differential System GE Multilin E 2 DNP POINT LISTS APPENDIX E E ...
Page 634: ...F 12 L30 Line Current Differential System GE Multilin F 3 WARRANTY APPENDIX F F ...