5D55
...Repeated for Ground Time Overcurrent 6
Ground Instantaneous Overcurrent (Read/Write Grouped Setting) (12 modules)
5DA0
Ground Instantaneous Overcurrent 1 Function
0 to 1
---
1
F102
0 (Disabled)
5DA1
Ground Instantaneous Overcurrent 1 Signal Source
0 to 5
---
1
F167
0 (SRC 1)
5DA2
Ground Instantaneous Overcurrent 1 Pickup
0 to 30
pu
0.001
F001
1000
5DA3
Ground Instantaneous Overcurrent 1 Delay
0 to 600
s
0.01
F001
0
5DA4
Ground Instantaneous Overcurrent 1 Reset Delay
0 to 600
s
0.01
F001
0
5DA5
Ground Instantaneous Overcurrent 1 Block
0 to 4294967295
---
1
F300
0
5DA7
Ground Instantaneous Overcurrent 1 Target
0 to 2
---
1
F109
0 (Self-reset)
5DA8
Ground Instantaneous Overcurrent 1 Events
0 to 1
---
1
F102
0 (Disabled)
5DA9
Reserved (8 items)
0 to 1
---
1
F001
0
5DB1
...Repeated for Ground Instantaneous Overcurrent 2
5DC2
...Repeated for Ground Instantaneous Overcurrent 3
5DD3
...Repeated for Ground Instantaneous Overcurrent 4
5DE4
...Repeated for Ground Instantaneous Overcurrent 5
5DF5
...Repeated for Ground Instantaneous Overcurrent 6
5E06
...Repeated for Ground Instantaneous Overcurrent 7
5E17
...Repeated for Ground Instantaneous Overcurrent 8
5E28
...Repeated for Ground Instantaneous Overcurrent 9
5E39
...Repeated for Ground Instantaneous Overcurrent 10
5E4A
...Repeated for Ground Instantaneous Overcurrent 11
5E5B
...Repeated for Ground Instantaneous Overcurrent 12
CT Fail (Read/Write Setting) (6 modules)
5E6C
CT Fail 1 Function
0 to 1
---
1
F102
0 (Disabled)
5E6D
CT Fail 1 Block
0 to 4294967295
---
1
F300
0
5E6F
CT Fail 1 Current Source 1
0 to 5
---
1
F167
0 (SRC 1)
5E70
CT Fail 1 Current Pickup 1
0 to 2
pu
0.1
F001
2
5E71
CT Fail 1 Current Source 2
0 to 5
---
1
F167
1 (SRC 2)
5E72
CT Fail 1 Current Pickup 2
0 to 2
pu
0.1
F001
2
5E73
CT Fail 1 Voltage Source
0 to 5
---
1
F167
0 (SRC 1)
5E74
CT Fail 1 Voltage Pickup
0 to 2
pu
0.01
F001
20
5E75
CT Fail 1 Pickup Delay
0 to 65.535
s
0.001
F001
1000
5E76
CT Fail 1 Target
0 to 2
---
1
F109
0 (Self-reset)
5E77
CT Fail 1 Events
0 to 1
---
1
F102
0 (Disabled)
5E78
...Repeated for CT Fail 2
5E84
...Repeated for CT Fail 3
5E90
...Repeated for CT Fail 4
5E9C
...Repeated for CT Fail 5
5EA8
...Repeated for CT Fail 6
Stub Bus (Read/Write Grouped Setting)
5F10
Stub Bus Function
0 to 1
---
1
F102
0 (Disabled)
5F11
Stub Bus Disconnect
0 to 4294967295
---
1
F300
0
5F13
Stub Bus Trigger
0 to 4294967295
---
1
F300
0
5F15
Stub Bus Target
0 to 2
---
1
F109
0 (Self-reset)
5F17
Stub Bus Events
0 to 1
---
1
F102
0 (Disabled)
50DD Disturbance Detection (Read/Write Grouped Setting)
5F20
50DD Function
0 to 1
---
1
F102
0 (Disabled)
5F21
50DD Non Current Supervision
0 to 4294967295
---
1
F300
0
5F23
50DD Control Logic
0 to 4294967295
---
1
F300
0
5F25
50DD Logic Seal In
0 to 4294967295
---
1
F300
0
5F27
50DD Events
0 to 1
---
1
F102
0 (Disabled)
Setting Groups (Read/Write Setting)
5F70
Setting Group for Modbus Comms (0 means group 1)
0 to 5
---
1
F001
0
5F71
Setting Groups Block
0 to 4294967295
---
1
F300
0
Table B–9: MODBUS MEMORY MAP (Sheet 29 of 61)
ADDR
REGISTER NAME
RANGE
UNITS
STEP
FORMAT
DEFAULT
Summary of Contents for L30
Page 10: ...x L30 Line Current Differential System GE Multilin TABLE OF CONTENTS ...
Page 30: ...1 20 L30 Line Current Differential System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Page 370: ...5 244 L30 Line Current Differential System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Page 464: ...A 10 L30 Line Current Differential System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Page 600: ...C 30 L30 Line Current Differential System GE Multilin C 7 LOGICAL NODES APPENDIX C C ...
Page 610: ...D 10 L30 Line Current Differential System GE Multilin D 1 IEC 60870 5 104 APPENDIX D D ...
Page 622: ...E 12 L30 Line Current Differential System GE Multilin E 2 DNP POINT LISTS APPENDIX E E ...
Page 634: ...F 12 L30 Line Current Differential System GE Multilin F 3 WARRANTY APPENDIX F F ...
Page 644: ...x L30 Line Current Differential System GE Multilin INDEX ...