5-42
L30 Line Current Differential System
GE Multilin
5.2 PRODUCT SETUP
5 SETTINGS
5
The disconnect switch configuration settings are shown below. Changes to these values will not take effect until the UR is
restarted:
PATH: SETTINGS
PRODUCT SETUP
COMMUNICATIONS
IEC 61850 PROTOCOL
XSWI CONFIGURATION
The
CLEAR XSWI1 OpCnt
setting represents the disconnect switch operating counter. As disconnect switches operate by
opening and closing, the XSWI operating counter status attribute (OpCnt) increments with every operation. Frequent switch
operation may result in very large OpCnt values over time. This setting allows the OpCnt to be reset to “0” for XSWI1.
Since GSSE/GOOSE messages are multicast Ethernet by specification, they will not usually be forwarded by net-
work routers. However, GOOSE messages may be forwarded by routers if the router has been configured for VLAN
functionality.
i) WEB SERVER HTTP PROTOCOL
PATH: SETTINGS
PRODUCT SETUP
COMMUNICATIONS
WEB SERVER HTTP PROTOCOL
The L30 contains an embedded web server and is capable of transferring web pages to a web browser such as Internet
Explorer or Firefox. This feature is available when the L30 has the Ethernet option installed. The web pages are organized
as a series of menus that can be accessed starting at the L30 “Main Menu”. Web pages are available showing DNP and
IEC 60870-5-104 points lists, Modbus registers, event records, fault reports, and so on. First connect the UR and a com-
puter to an Ethernet network, then enter the IP address of the L30 into the “Address” box of the web browser.
j) TFTP PROTOCOL
PATH: SETTINGS
PRODUCT SETUP
COMMUNICATIONS
TFTP PROTOCOL
XSWI
CONFIGURATION
XSWI1 ST.LOC OPERAND
Off
Range: FlexLogic operand
MESSAGE
XSWI2 ST.LOC OPERAND
Off
Range: FlexLogic operand
MESSAGE
XSWI3 ST.LOC OPERAND
Off
Range: FlexLogic operand
MESSAGE
XSWI24 ST.LOC OPERAND
Off
Range: FlexLogic operand
MESSAGE
CLEAR XSWI1 OpCnt:
No
Range: No, Yes
MESSAGE
CLEAR XSWI2 OpCnt:
No
Range: No, Yes
MESSAGE
CLEAR XSWI3 OpCnt:
No
Range: No, Yes
MESSAGE
CLEAR XSWI24 OpCnt:
No
Range: No, Yes
WEB SERVER
HTTP PROTOCOL
HTTP TCP PORT
NUMBER: 80
Range: 0 to 65535 in steps of 1
TFTP PROTOCOL
TFTP MAIN UDP PORT
NUMBER: 69
Range: 0 to 65535 in steps of 1
MESSAGE
TFTP DATA UDP PORT 1
NUMBER: 0
Range: 0 to 65535 in steps of 1
MESSAGE
TFTP DATA UDP PORT 2
NUMBER: 0
Range: 0 to 65535 in steps of 1
NOTE
Summary of Contents for L30
Page 10: ...x L30 Line Current Differential System GE Multilin TABLE OF CONTENTS ...
Page 30: ...1 20 L30 Line Current Differential System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Page 370: ...5 244 L30 Line Current Differential System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Page 464: ...A 10 L30 Line Current Differential System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Page 600: ...C 30 L30 Line Current Differential System GE Multilin C 7 LOGICAL NODES APPENDIX C C ...
Page 610: ...D 10 L30 Line Current Differential System GE Multilin D 1 IEC 60870 5 104 APPENDIX D D ...
Page 622: ...E 12 L30 Line Current Differential System GE Multilin E 2 DNP POINT LISTS APPENDIX E E ...
Page 634: ...F 12 L30 Line Current Differential System GE Multilin F 3 WARRANTY APPENDIX F F ...
Page 644: ...x L30 Line Current Differential System GE Multilin INDEX ...