GE Multilin
L30 Line Current Differential System
5-43
5 SETTINGS
5.2 PRODUCT SETUP
5
The Trivial File Transfer Protocol (TFTP) can be used to transfer files from the L30 over a network. The L30 operates as a
TFTP server. TFTP client software is available from various sources, including Microsoft Windows NT. The
dir.txt
file
obtained from the L30 contains a list and description of all available files (event records, oscillography, etc.).
k) IEC 60870-5-104 PROTOCOL
PATH: SETTINGS
PRODUCT SETUP
COMMUNICATIONS
IEC 60870-5-104 PROTOCOL
The L30 supports the IEC 60870-5-104 protocol. The L30 can be used as an IEC 60870-5-104 slave device connected to a
maximum of two masters (usually either an RTU or a SCADA master station). Since the L30 maintains two sets of IEC
60870-5-104 data change buffers, no more than two masters should actively communicate with the L30 at one time.
The
IEC ------- DEFAULT THRESHOLD
settings are used to determine when to trigger spontaneous responses containing
M_ME_NC_1 analog data. These settings group the L30 analog data into types: current, voltage, power, energy, and other.
Each setting represents the default threshold value for all M_ME_NC_1 analog points of that type. For example, to trigger
spontaneous responses from the L30 when any current values change by 15 A, the
IEC CURRENT DEFAULT THRESHOLD
set-
ting should be set to 15. Note that these settings are the default values of the deadbands. P_ME_NC_1 (parameter of mea-
sured value, short floating point value) points can be used to change threshold values, from the default, for each individual
M_ME_NC_1 analog point. Whenever power is removed and re-applied to the L30, the default thresholds are in effect.
The L30 relay does not support energy metering. As such, the
IEC ENERGY DEFAULT THRESHOLD
setting is not appli-
cable.
The IEC 60870-5-104 and DNP protocols cannot be used simultaneously. When the IEC 60870-5-104 FUNCTION
setting is set to “Enabled”, the DNP protocol does not operate. When this setting is changed, it takes effect when
power to the relay is cycled (off-to-on).
IEC 60870-5-104
PROTOCOL
IEC 60870-5-104
FUNCTION: Disabled
Range: Enabled, Disabled
MESSAGE
IEC TCP PORT
NUMBER: 2404
Range: 0 to 65535 in steps of 1
MESSAGE
IEC NETWORK
CLIENT ADDRESSES
MESSAGE
IEC COMMON ADDRESS
OF ASDU:
0
Range: 0 to 65535 in steps of 1
MESSAGE
IEC CYCLIC DATA
PERIOD:
60 s
Range: 1 to 65535 s in steps of 1
MESSAGE
IEC CURRENT DEFAULT
THRESHOLD: 30000
Range: 0 to 65535 in steps of 1
MESSAGE
IEC VOLTAGE DEFAULT
THRESHOLD: 30000
Range: 0 to 65535 in steps of 1
MESSAGE
IEC POWER DEFAULT
THRESHOLD: 30000
Range: 0 to 65535 in steps of 1
MESSAGE
IEC ENERGY DEFAULT
THRESHOLD: 30000
Range: 0 to 65535 in steps of 1
MESSAGE
IEC OTHER DEFAULT
THRESHOLD: 30000
Range: 0 to 65535 in steps of 1
NOTE
NOTE
Summary of Contents for L30
Page 10: ...x L30 Line Current Differential System GE Multilin TABLE OF CONTENTS ...
Page 30: ...1 20 L30 Line Current Differential System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Page 370: ...5 244 L30 Line Current Differential System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Page 464: ...A 10 L30 Line Current Differential System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Page 600: ...C 30 L30 Line Current Differential System GE Multilin C 7 LOGICAL NODES APPENDIX C C ...
Page 610: ...D 10 L30 Line Current Differential System GE Multilin D 1 IEC 60870 5 104 APPENDIX D D ...
Page 622: ...E 12 L30 Line Current Differential System GE Multilin E 2 DNP POINT LISTS APPENDIX E E ...
Page 634: ...F 12 L30 Line Current Differential System GE Multilin F 3 WARRANTY APPENDIX F F ...
Page 644: ...x L30 Line Current Differential System GE Multilin INDEX ...