5.2 PRODUCT SETUP
5 SETTINGS
5
Refer to the
LED indicators
section in chapter 4 for additional information on the location of these indexed LEDs.
The user-programmable LED settings select the FlexLogic operands that control the LEDs. If the
LED 1 TYPE
setting is “Self-
Reset” (the default setting), the LED illumination will track the state of the selected LED operand. If the
LED 1 TYPE
setting is
“Latched”, the LED, once lit, remains so until reset by the faceplate RESET button, from a remote device via a communica-
tions channel, or from any programmed operand, even if the LED operand state de-asserts.
5.2.12 USER-PROGRAMMABLE SELF-TESTS
For user-programmable self-tests for CyberSentry, use the
Setup > Security > Supervisory
menu instead.
PATH: SETTINGS
PRODUCT SETUP
USER-PROGRAMMABLE SELF TESTS
All major self-test alarms are reported automatically with their corresponding FlexLogic operands, events, and targets. Most
of the minor alarms can be disabled if desired.
Table 5–4: RECOMMENDED SETTINGS FOR USER-PROGRAMMABLE LEDS
SETTING
PARAMETER
SETTING
PARAMETER
LED 1 operand
SETTING GROUP ACT 1
LED 13 operand
Off
LED 2 operand
SETTING GROUP ACT 2
LED 14 operand
BREAKER 2 OPEN
LED 3 operand
SETTING GROUP ACT 3
LED 15 operand
BREAKER 2 CLOSED
LED 4 operand
SETTING GROUP ACT 4
LED 16 operand
BREAKER 2 TROUBLE
LED 5 operand
SETTING GROUP ACT 5
LED 17 operand
SYNC 1 SYNC OP
LED 6 operand
SETTING GROUP ACT 6
LED 18 operand
SYNC 2 SYNC OP
LED 7 operand
Off
LED 19 operand
Off
LED 8 operand
Off
LED 20 operand
Off
LED 9 operand
BREAKER 1 OPEN
LED 21 operand
AR ENABLED
LED 10 operand
BREAKER 1 CLOSED
LED 22 operand
AR DISABLED
LED 11 operand
BREAKER 1 TROUBLE
LED 23 operand
AR RIP
LED 12 operand
Off
LED 24 operand
AR LO
USER-PROGRAMMABLE
SELF TESTS
REMOTE DEVICE OFF
FUNCTION: Enabled
Range: Disabled, Enabled.
MESSAGE
PRI. ETHERNET FAIL
FUNCTION: Disabled
Range: Disabled, Enabled.
MESSAGE
SEC. ETHERNET FAIL
FUNCTION: Disabled
Range: Disabled, Enabled.
MESSAGE
THIRD ETHERNET FAIL
FUNCTION: Disabled
Range: Disabled, Enabled.
MESSAGE
BATTERY FAIL
FUNCTION: Enabled
Range: Disabled, Enabled.
MESSAGE
SNTP FAIL
FUNCTION: Enabled
Range: Disabled, Enabled.
MESSAGE
IRIG-B FAIL
FUNCTION: Enabled
Range: Disabled, Enabled.
MESSAGE
PTP FAIL
FUNCTION: Enabled
Range: Disabled, Enabled.
MESSAGE
SFP MODULE FAIL
FUNCTION: Disabled
Range: Disabled, Enabled.
Summary of Contents for L30
Page 10: ...x L30 Line Current Differential System GE Multilin TABLE OF CONTENTS ...
Page 30: ...1 20 L30 Line Current Differential System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Page 370: ...5 244 L30 Line Current Differential System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Page 464: ...A 10 L30 Line Current Differential System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Page 600: ...C 30 L30 Line Current Differential System GE Multilin C 7 LOGICAL NODES APPENDIX C C ...
Page 610: ...D 10 L30 Line Current Differential System GE Multilin D 1 IEC 60870 5 104 APPENDIX D D ...
Page 622: ...E 12 L30 Line Current Differential System GE Multilin E 2 DNP POINT LISTS APPENDIX E E ...
Page 634: ...F 12 L30 Line Current Differential System GE Multilin F 3 WARRANTY APPENDIX F F ...
Page 644: ...x L30 Line Current Differential System GE Multilin INDEX ...