5-114
L30 Line Current Differential System
GE Multilin
5.4 SYSTEM SETUP
5 SETTINGS
5
PATH: SETTINGS
SYSTEM SETUP
PHASOR MEASUREMENT UNIT
PMU AGGREGATOR 1
37.118 AGGR 1 CONFIG-
URATION
PATH: SETTINGS
SYSTEM SETUP
PHASOR MEASUREMENT UNIT
PMU AGGREGATOR 1
90-5 AGGR 1 CONFIGU-
RATION
•
PMU AGGREGATOR1 PROTOCOL
: This setting selects if C37.118 or the new IEC61850 standard will be used.
•
PMU AGGREGATOR1 IDCODE
: Numeric identifier of the Aggregator / PDC function. In an IEEE C37.118 output
stream, this identifies the ID of the aggregator - which is only used if there is more than 1 PMU mapped into an aggre-
gator.
•
AGGREGATOR1: PHYSICAL PORT:
This setting determines which physical ports through which the synchrophasor
traffic will be transmitted. The range is 1, 2, 3.
•
PMU AGGREGATOR1 PMU1 to PMU4
: If set to “Yes” aggregator 1 includes the PMU1 data set in the reporting data
stream. AGGREGATOR1 will not include PMU1 data set in the report if set to “No”.
C37.118 AGGREGATOR 1 CONFIGURATION
•
PMU AGGREGATOR1: TCP PORT
: This setting selects the TCP port number that will be used by this aggregator for
network reporting. When using more than one aggregator, the default value of the port must be properly changed to
avoid port number collisions.
•
PMU AGGREGATOR1 UDP PORT
: This setting selects the UDP port number that will be used by this aggregator for
network reporting. When using more than one aggregator, the default value of the port must be properly changed to
avoid port number collisions.
•
PMU AGGREGATOR1 PDC CONTROL
: The synchrophasor standard allows for user-defined controls originating at
the PDC, to be executed on the PMU. The control is accomplished via an extended command frame. The relay
decodes the first word of the extended field, EXTFRAME, to drive 16 dedicated FlexLogic operands. Each aggregator
supports 16 FlexLogic operands as shown in table 2. The operands are asserted for 5 seconds following reception of
the command frame. If the new command frame arrives within the 5 second period, the FlexLogic operands are
updated, and the 5 second timer is re-started. This setting enables or disables the control. When enabled, all 16 oper-
ands for each aggregator are active; when disabled all 16 operands for each aggregator remain reset.
37.118 AGGR 1
CONFIGURATION
PMU AGGREGATOR 1
TCP PORT: 4712
Range: 1 to 65534
Default: 4712
MESSAGE
PMU AGGREGATOR 1
UDP PORT: 4713
Range: 1 to 65534
Default: 4713
MESSAGE
PMU AGGREGATOR 1
PDC CONTROL: Disabled
Range: Disabled, Enabled
Default: Disabled
90-5 AGGR 1
CONFIGURATION
PMU AGGREGATOR 1
NAME:
Range: 56 character ASCII text
Default: Blank
MESSAGE
PMU AGGREGATOR 1:
UDP PORT: 102
Range: 1 to 65534 in steps of 1
Default: 102
MESSAGE
PMU AGGREGATOR 1:
NUMBER OF ASDUs: 1
Range: 1 to 4
Default: 1
Table 5–7: FLEXLOGIC OPERANDS SUPPORTED BY AGGREGATOR
OPERAND TYPE
OPERAND SYNTAX
OPERAND DESCRIPTION
ELEMENT:
Synchrophasor, phasor data,
concentrator
AGTR1 PDC CNTRL 1
Phasor data concentrator asserts control bit 1, as
received via the network.
as above
AGTR1 PDC CNTRL 2
Phasor data concentrator asserts control bit 2 as
received via the network.
as above
AGTR1 PDC CNTRL 3
Phasor data concentrator asserts control bit 3 as
received via the network.
as above
AGTR1 PDC CNTRL 16
Phasor data concentrator asserts control bit 16, as
received via the network.
Summary of Contents for L30
Page 10: ...x L30 Line Current Differential System GE Multilin TABLE OF CONTENTS ...
Page 30: ...1 20 L30 Line Current Differential System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Page 370: ...5 244 L30 Line Current Differential System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Page 464: ...A 10 L30 Line Current Differential System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Page 600: ...C 30 L30 Line Current Differential System GE Multilin C 7 LOGICAL NODES APPENDIX C C ...
Page 610: ...D 10 L30 Line Current Differential System GE Multilin D 1 IEC 60870 5 104 APPENDIX D D ...
Page 622: ...E 12 L30 Line Current Differential System GE Multilin E 2 DNP POINT LISTS APPENDIX E E ...
Page 634: ...F 12 L30 Line Current Differential System GE Multilin F 3 WARRANTY APPENDIX F F ...
Page 644: ...x L30 Line Current Differential System GE Multilin INDEX ...