GE Multilin
L30 Line Current Differential System
5-115
5 SETTINGS
5.4 SYSTEM SETUP
5
IEC61850-90-5 AGGREGATOR 1 CONFIGURATION
•
PMU AGGREGATOR1: NAME:
A user-defined visible string of characters (max. 56) to identify the source of the
stream. This value, concatenated with the Aggregator IDCode and Aggregator Class of Service, is mapped into the
IEC61850 MSVID filed in the output stream.
•
PMU AGGREGATOR1: UDP:
This setting selects the UDP port number that is used by this dataset for network report-
ing. Default setting values for C37.118 and IEC6150-90-5 are provided.
•
PMU AGGREGATOR1: #OF ASDUs:
This setting sets the number of ASDU’s per from 1 through to 4. Refer to the
table below.
m) CONTROL BLOCKS
PATH: SETTINGS
SYSTEM SETUP
PHASOR MEASUREMENT UNIT
IEC 90 – 5 MSVCB01 CONFIGURATION
as above
AGTR2 PDC CNTRL 1
Phasor data concentrator asserts control bit 1 as
received via the network
as above
AGTR2 PDC CNTRL 2
Phasor data concentrator asserts control bit 2 as
received via the network
as above
AGTR2 PDC CNTRL 3
Phasor data concentrator asserts control bit 3 as
received via the network.
as above
AGTR1 PDC CNTRL 16
Phasor data concentrator asserts control bit 16, as
received via the network.
Table 5–8: # OF ASDU
SETTINGS FOR # OF ASDU
TRANSMISSION
1
ASDU at T0 (current values)
2
ASDU at T-1 (previous values) + ASDU at T0 (current values)
3
ASDU at T-2 (previous values) + ASDU at T-1 (previous ASDU at T0 (current
values)
4
ASDU at T-3 (previous values) + ASDU at T-2 (previous values) + ASDU at T-1 (previous
ASDU at T0 (current values)
IEC 90-5 MSVCB
CONFIGURATION
MSVCB 1 SVENA:
OFF
Range: Flexlogic Operand
Default: Off
MESSAGE
MSVCB 1 CLIENT CTRL:
OFF
Range: Flexlogic Operand
Default: Off
MESSAGE
MSVCB 1 SVENA DEFLT:
OFF
Range: Flexlogic Operand
Default: Off
MESSAGE
MSVCB 1 CONFREV:
1
Range: 1 to 4294967295
Default: 1
MESSAGE
MSVCB 1 PRIORITY:
4
Range: 0 to 7
Default: 4
MESSAGE
MSVCB 1 IP CLASS:
46
Range: 0 to 252
Default: 46
MESSAGE
MSVCB 1 VID:
0
Range: 0 to 4095
Default: 0
MESSAGE
MSVCB 1 APPID:
0
Range: 0 to 16383
Default: 0
Table 5–7: FLEXLOGIC OPERANDS SUPPORTED BY AGGREGATOR
OPERAND TYPE
OPERAND SYNTAX
OPERAND DESCRIPTION
Summary of Contents for L30
Page 10: ...x L30 Line Current Differential System GE Multilin TABLE OF CONTENTS ...
Page 30: ...1 20 L30 Line Current Differential System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Page 370: ...5 244 L30 Line Current Differential System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Page 464: ...A 10 L30 Line Current Differential System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Page 600: ...C 30 L30 Line Current Differential System GE Multilin C 7 LOGICAL NODES APPENDIX C C ...
Page 610: ...D 10 L30 Line Current Differential System GE Multilin D 1 IEC 60870 5 104 APPENDIX D D ...
Page 622: ...E 12 L30 Line Current Differential System GE Multilin E 2 DNP POINT LISTS APPENDIX E E ...
Page 634: ...F 12 L30 Line Current Differential System GE Multilin F 3 WARRANTY APPENDIX F F ...
Page 644: ...x L30 Line Current Differential System GE Multilin INDEX ...