GE Multilin
L30 Line Current Differential System
5-133
5 SETTINGS
5.5 FLEXLOGIC
5
•
TIMER 1 DROPOUT DELAY:
Sets the time delay to dropout. If a dropout delay is not required, set this function to "0".
5.5.7 FLEXELEMENTS
PATH: SETTING
FLEXLOGIC
FLEXELEMENTS
FLEXELEMENT 1(8)
A FlexElement is a universal comparator that can be used to monitor any analog actual value calculated by the relay or a
net difference of any two analog actual values of the same type. The effective operating signal could be treated as a signed
number or its absolute value could be used as per user's choice.
The element can be programmed to respond either to a signal level or to a rate-of-change (delta) over a pre-defined period
of time. The output operand is asserted when the operating signal is higher than a threshold or lower than a threshold as
per user's choice.
FLEXELEMENT 1
FLEXELEMENT 1
FUNCTION: Disabled
Range: Disabled, Enabled
MESSAGE
FLEXELEMENT 1 NAME:
FxE1
Range: up to 6 alphanumeric characters
MESSAGE
FLEXELEMENT 1 +IN:
Off
Range: Off, any analog actual value parameter
MESSAGE
FLEXELEMENT 1 -IN:
Off
Range: Off, any analog actual value parameter
MESSAGE
FLEXELEMENT 1 INPUT
MODE: Signed
Range: Signed, Absolute
MESSAGE
FLEXELEMENT 1 COMP
MODE: Level
Range: Level, Delta
MESSAGE
FLEXELEMENT 1
DIRECTION: Over
Range: Over, Under
MESSAGE
FLEXELEMENT 1
PICKUP: 1.000 pu
Range: –90.000 to 90.000 pu in steps of 0.001
MESSAGE
FLEXELEMENT 1
HYSTERESIS: 3.0%
Range: 0.1 to 50.0% in steps of 0.1
MESSAGE
FLEXELEMENT 1 dt
UNIT: milliseconds
Range: milliseconds, seconds, minutes
MESSAGE
FLEXELEMENT 1 dt:
20
Range: 20 to 86400 in steps of 1
MESSAGE
FLEXELEMENT 1 PKP
DELAY: 0.000 s
Range: 0.000 to 65.535 s in steps of 0.001
MESSAGE
FLEXELEMENT 1 RST
DELAY: 0.000 s
Range: 0.000 to 65.535 s in steps of 0.001
MESSAGE
FLEXELEMENT 1 BLK:
Off
Range: FlexLogic operand
MESSAGE
FLEXELEMENT 1
TARGET: Self-reset
Range: Self-reset, Latched, Disabled
MESSAGE
FLEXELEMENT 1
EVENTS: Disabled
Range: Disabled, Enabled
Summary of Contents for L30
Page 10: ...x L30 Line Current Differential System GE Multilin TABLE OF CONTENTS ...
Page 30: ...1 20 L30 Line Current Differential System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Page 370: ...5 244 L30 Line Current Differential System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Page 464: ...A 10 L30 Line Current Differential System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Page 600: ...C 30 L30 Line Current Differential System GE Multilin C 7 LOGICAL NODES APPENDIX C C ...
Page 610: ...D 10 L30 Line Current Differential System GE Multilin D 1 IEC 60870 5 104 APPENDIX D D ...
Page 622: ...E 12 L30 Line Current Differential System GE Multilin E 2 DNP POINT LISTS APPENDIX E E ...
Page 634: ...F 12 L30 Line Current Differential System GE Multilin F 3 WARRANTY APPENDIX F F ...
Page 644: ...x L30 Line Current Differential System GE Multilin INDEX ...