GE Multilin
L30 Line Current Differential System
5-209
5 SETTINGS
5.7 CONTROL ELEMENTS
5
5.7.10 MONITORING ELEMENTS
a) MAIN MENU
PATH: SETTINGS
CONTROL ELEMENTS
MONITORING ELEMENTS
b) BREAKER ARCING CURRENT
PATH: SETTINGS
CONTROL ELEMENTS
MONITORING ELEMENTS
BREAKER 1(2) ARCING CURRENT
MONITORING
ELEMENTS
BREAKER 1
ARCING CURRENT
MESSAGE
BREAKER 2
ARCING CURRENT
MESSAGE
CT FAILURE
DETECTOR
MESSAGE
VT FUSE FAILURE 1
MESSAGE
VT FUSE FAILURE 2
MESSAGE
BROKEN CONDUCTOR 1
MESSAGE
BROKEN CONDUCTOR 2
MESSAGE
THERMAL OVERLOAD
PROTECTION
BREAKER 1
ARCING CURRENT
BKR 1 ARC AMP
FUNCTION: Disabled
Range: Disabled, Enabled
MESSAGE
BKR 1 ARC AMP
SOURCE: SRC 1
Range: SRC 1, SRC 2
MESSAGE
BKR 1 ARC AMP INT-A:
Off
Range: FlexLogic™ operand
MESSAGE
BKR 1 ARC AMP INT-B:
Off
Range: FlexLogic™ operand
MESSAGE
BKR 1 ARC AMP INT-C:
Off
Range: FlexLogic™ operand
MESSAGE
BKR 1 ARC AMP
DELAY: 0.000
s
Range: 0.000 to 65.535 s in steps of 0.001
MESSAGE
BKR 1 ARC AMP LIMIT:
1000 kA2-cyc
Range: 0 to 50000 kA
2
-cycle in steps of 1
MESSAGE
BKR 1 ARC AMP BLOCK:
Off
Range: FlexLogic™ operand
MESSAGE
BKR 1 ARC AMP
TARGET: Self-reset
Range: Self-reset, Latched, Disabled
MESSAGE
BKR 1 ARC AMP
EVENTS: Disabled
Range: Disabled, Enabled
Summary of Contents for L30
Page 10: ...x L30 Line Current Differential System GE Multilin TABLE OF CONTENTS ...
Page 30: ...1 20 L30 Line Current Differential System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Page 370: ...5 244 L30 Line Current Differential System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Page 464: ...A 10 L30 Line Current Differential System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Page 600: ...C 30 L30 Line Current Differential System GE Multilin C 7 LOGICAL NODES APPENDIX C C ...
Page 610: ...D 10 L30 Line Current Differential System GE Multilin D 1 IEC 60870 5 104 APPENDIX D D ...
Page 622: ...E 12 L30 Line Current Differential System GE Multilin E 2 DNP POINT LISTS APPENDIX E E ...
Page 634: ...F 12 L30 Line Current Differential System GE Multilin F 3 WARRANTY APPENDIX F F ...
Page 644: ...x L30 Line Current Differential System GE Multilin INDEX ...