6-12
L30 Line Current Differential System
GE Multilin
6.3 METERING
6 ACTUAL VALUES
6
b) UR CONVENTION FOR MEASURING PHASE ANGLES
All phasors calculated by UR-series relays and used for protection, control and metering functions are rotating phasors that
maintain the correct phase angle relationships with each other at all times.
For display and oscillography purposes, all phasor angles in a given relay are referred to an AC input channel pre-selected
by the
SETTINGS
SYSTEM SETUP
POWER SYSTEM
FREQUENCY AND PHASE REFERENCE
setting. This setting
defines a particular AC signal source to be used as the reference.
The relay will first determine if any “Phase VT” bank is indicated in the source. If it is, voltage channel VA of that bank is
used as the angle reference. Otherwise, the relay determines if any “Aux VT” bank is indicated; if it is, the auxiliary voltage
channel of that bank is used as the angle reference. If neither of the two conditions is satisfied, then two more steps of this
hierarchical procedure to determine the reference signal include “Phase CT” bank and “Ground CT” bank.
If the AC signal pre-selected by the relay upon configuration is not measurable, the phase angles are not referenced. The
phase angles are assigned as positive in the leading direction, and are presented as negative in the lagging direction, to
more closely align with power system metering conventions. This is illustrated below.
Figure 6–2: UR PHASE ANGLE MEASUREMENT CONVENTION
c) UR CONVENTION FOR MEASURING SYMMETRICAL COMPONENTS
The UR-series of relays calculate voltage symmetrical components for the power system phase A line-to-neutral voltage,
and symmetrical components of the currents for the power system phase A current. Owing to the above definition, phase
angle relations between the symmetrical currents and voltages stay the same irrespective of the connection of instrument
transformers. This is important for setting directional protection elements that use symmetrical voltages.
For display and oscillography purposes the phase angles of symmetrical components are referenced to a common refer-
ence as described in the previous sub-section.
WYE-CONNECTED INSTRUMENT TRANSFORMERS:
The above equations apply to currents as well.
•
ABC phase rotation:
•
ACB phase rotation:
827845A1.CDR
UR phase angle
reference
0
o
-45
o
-90
o
-135
o
-270
o
-225
o
-180
o
-315
o
positive
angle
direction
V_0
1
3
---
V
AG
V
BG
V
CG
+
+
=
V_1
1
3
---
V
AG
aV
BG
a
2
V
CG
+
+
=
V_2
1
3
---
V
AG
a
2
V
BG
aV
CG
+
+
=
V_0
1
3
---
V
AG
V
BG
V
CG
+
+
=
V_1
1
3
---
V
AG
a
2
V
BG
aV
CG
+
+
=
V_2
1
3
---
V
AG
aV
BG
a
2
V
CG
+
+
=
Summary of Contents for L30
Page 10: ...x L30 Line Current Differential System GE Multilin TABLE OF CONTENTS ...
Page 30: ...1 20 L30 Line Current Differential System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Page 370: ...5 244 L30 Line Current Differential System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Page 464: ...A 10 L30 Line Current Differential System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Page 600: ...C 30 L30 Line Current Differential System GE Multilin C 7 LOGICAL NODES APPENDIX C C ...
Page 610: ...D 10 L30 Line Current Differential System GE Multilin D 1 IEC 60870 5 104 APPENDIX D D ...
Page 622: ...E 12 L30 Line Current Differential System GE Multilin E 2 DNP POINT LISTS APPENDIX E E ...
Page 634: ...F 12 L30 Line Current Differential System GE Multilin F 3 WARRANTY APPENDIX F F ...
Page 644: ...x L30 Line Current Differential System GE Multilin INDEX ...