2-26
L30 Line Current Differential System
GE Multilin
2.4 SPECIFICATIONS
2 PRODUCT DESCRIPTION
2
2.4.11 TYPE TESTS
L30 TYPE TESTS
2.4.12 PRODUCTION TESTS
THERMAL
Products go through an environmental test based upon an
Accepted Quality Level (AQL) sampling process.
TEST
REFERENCE STANDARD
TEST LEVEL
Dielectric voltage withstand
EN60255-5
2.2 kV
Impulse voltage withstand
EN60255-5
5 kV
Damped oscillatory
IEC61000-4-18 / IEC60255-22-1
2.5 kV CM, 1 kV DM
Electrostatic discharge
EN61000-4-2 / IEC60255-22-2
Level 3
RF immunity
EN61000-4-3 / IEC60255-22-3
Level 3
Fast transient disturbance
EN61000-4-4 / IEC60255-22-4
Class A and B
Surge immunity
EN61000-4-5 / IEC60255-22-5
Level 3 and 4
Conducted RF immunity
EN61000-4-6 / IEC60255-22-6
Level 3
Power frequency immunity
EN61000-4-7 / IEC60255-22-7
Class A and B
Voltage interruption and ripple DC
IEC60255-11
12% ripple, 200 ms interrupts
Radiated and conducted emissions
CISPR11 / CISPR22 / IEC60255-25
Class A
Sinusoidal vibration
IEC60255-21-1
Class 1
Shock and bump
IEC60255-21-2
Class 1
Seismic
IEC60255-21-3
Class 1
Power magnetic immunity
IEC61000-4-8
Level 5
Pulse magnetic immunity
IEC61000-4-9
Level 4
Damped magnetic immunity
IEC61000-4-10
Level 4
Voltage dip and interruption
IEC61000-4-11
0, 40, 70, 80% dips; 250 / 300 cycle interrupts
Damped oscillatory
IEC61000-4-12
2.5 kV CM, 1 kV DM
Conducted RF immunity, 0 to 150 kHz
IEC61000-4-16
Level 4
Voltage ripple
IEC61000-4-17
15% ripple
Ingress protection
IEC60529
IP40 front, IP10 back
Cold
IEC60068-2-1
–40°C for 16 hours
Hot
IEC60068-2-2
85°C for 16 hours
Humidity
IEC60068-2-30
6 days, variant 1
Damped oscillatory
IEEE/ANSI C37.90.1
2.5 kV, 1 MHz
RF immunity
IEEE/ANSI C37.90.2
20 V/m, 80 MHz to 1 GHz
Safety
UL508
e83849 NKCR
Safety
UL C22.2-14
e83849 NKCR7
Safety
UL1053
e83849 NKCR
Summary of Contents for L30
Page 10: ...x L30 Line Current Differential System GE Multilin TABLE OF CONTENTS ...
Page 30: ...1 20 L30 Line Current Differential System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Page 370: ...5 244 L30 Line Current Differential System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Page 464: ...A 10 L30 Line Current Differential System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Page 600: ...C 30 L30 Line Current Differential System GE Multilin C 7 LOGICAL NODES APPENDIX C C ...
Page 610: ...D 10 L30 Line Current Differential System GE Multilin D 1 IEC 60870 5 104 APPENDIX D D ...
Page 622: ...E 12 L30 Line Current Differential System GE Multilin E 2 DNP POINT LISTS APPENDIX E E ...
Page 634: ...F 12 L30 Line Current Differential System GE Multilin F 3 WARRANTY APPENDIX F F ...
Page 644: ...x L30 Line Current Differential System GE Multilin INDEX ...