EPM 4
5
00 SUB METER – INSTRUCTION MANUAL
4–1
EPM4
5
00 Sub Meter
Chapter 4: Communications
GE
Energy
Industrial Solutions
709710A1.CDR
Communications
4.1
Modbus Communications
4.1.1
RS485 Wiring for Modbus
The wiring for Modbus communications for two-wire and four-wire RS485 is indicated
below.
For two-wire RS-485:
For four-wire RS-485:
Color
Function
DB-9 Pinout
Yellow
RX (+)
2
Black
TX (–)
8
Color
Function
DB-9 Pinout
Yellow (A)
RX (+)
2
Black (B)
RX (–)
3
Green (Y)
TX (+)
7
Red (Z)
TX (–)
8