background image

 

4.

 

Apply critical load stickers next to appropriate branch 
breakers for generator loads.

  

 
 
 
 

 

 

 

 

 

 

 

 
 
 
 
 

Figure  3:  Interlock  Installation

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

Interlock Operation 

To energize the panel from Generator Power: 

1.

 

Turn 

OFF

 the 2-pole main breaker

 

2.

 

Turn 

OFF

 all the branch circuit breakers

 

3.

 

Move the sliding plate on the interlock towards branch 
breakers using the tabs provided

 

4.

 

Turn 

ON

 the 2-pole back-fed main breaker 

5.

 

Turn 

ON

 the branch circuit breakers supplying critical 

circuits 

 

To energize the panel from Utility Power: 

1.

 

Turn 

OFF

 the 2-pole back-fed main breaker

 

2.

 

Turn 

OFF

 all branch circuit breakers

 

3.

 

Move the sliding plate on the interlock towards branch 
breakers using the tabs provided

 

4.

 

Turn 

ON

 the 2-pole main breaker 

5.

 

Turn 

ON

 the branch circuit breakers 

 

 

 

   

    

 

 

 

 