2
4.
Apply critical load stickers next to appropriate branch
breakers for generator loads.
Figure 3: Interlock Installation
Interlock Operation
To energize the panel from Generator Power:
1.
Turn
OFF
the 2-pole main breaker
2.
Turn
OFF
all the branch circuit breakers
3.
Move the sliding plate on the interlock towards branch
breakers using the tabs provided
4.
Turn
ON
the 2-pole back-fed main breaker
5.
Turn
ON
the branch circuit breakers supplying critical
circuits
To energize the panel from Utility Power:
1.
Turn
OFF
the 2-pole back-fed main breaker
2.
Turn
OFF
all branch circuit breakers
3.
Move the sliding plate on the interlock towards branch
breakers using the tabs provided
4.
Turn
ON
the 2-pole main breaker
5.
Turn
ON
the branch circuit breakers