CHAPTER 6: SETPOINTS
S1 RELAY SETUP
345 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL
6–17
The following path is available using the keypad. For instructions on how to use the
keypad, please refer to
Chapter 3 - Working with the Keypad
.
PATH
:
SETPOINTS > S1 RELAY SETUP > FAULT REPORT
FAULT RECORD TRIGGER
Range: Off, Any Trip, Contact Input 1 to 10, Virtual Input 1 to 32, Remote Input 1 to 32,
Logic Element 1 to 16
Default: Any Trip
This setting selects an operand for triggering the report. The report is triggered at the
rising edge of the selected trigger operand. To avoid inaccuracies during the fault
transient period, data from one cycle after the trigger is collected.
FAULT RECORD DELAY
Range: 0.00 to 600.00 s in steps of 0.01 s
Default: 0.00 s
This setting specifies the time delay after the first trip trigger for the Fault Report, during
which the record is not updated with any subsequent trip triggers.
Front panel with non-programmable LEDs
The user can send a message to the display, that will override any normal message by
sending text through Modbus. Refer to the
3 Series Communications Guide
for register
details.
PATH
:
SETPOINTS > S1 RELAY SETUP > FRONT PANEL
FLASH MESSAGE TIME
Range: 1 s to 65535 s
Default: 5 s
Flash messages are status, warning, error, or information messages displayed for
several seconds in response to certain key presses during setting programming. These
messages override any normal messages. The duration of a flash message on the
display can be changed to accommodate different reading rates.
MESSAGE TIMEOUT
Range: 1 s to 65535 s
Default: 30 s
If the keypad is inactive for a period of time, the relay automatically reverts to a default
message. The inactivity time is modified via this setting to ensure messages remain on
the screen long enough during programming or reading of actual values.
SCREEN SAVER
Range: Off, 1 min to 10000 min
Default: Off
The life of the LCD backlight can be prolonged by enabling the Screen Saver mode.
If the keypad is inactive for the selected period of time, the relay automatically shuts off
the LCD screen. Any activity (keypress, alarm, trip, or target message) will restore screen
messages.
W1 BKR OPEN COLOR
Range: Off, Red, Green, Orange
Default: Green
Allows the user to select the color of the LED indicator under Breaker Open conditions.