6–98
345 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL
S5 INPUTS/OUTPUTS
CHAPTER 6: SETPOINTS
Output Relay 1 - W1
breaker "Trip"
The following path is available using the keypad. For instructions on how to use the
keypad, please refer to
Chapter 3 - Working with the Keypad
.
PATH
:
SETPOINTS > S5 INPUTS/OUTPUTS > OUTPUT RELAYS > RLY 1 W1 BKRTRIP
RLY1 SEAL-IN
Range: 0.00 to 9.99 s in steps of 0.01
Default: 0.04 s
This setting defines the time to be added to the reset time of the Relay 1 Trip output,
thus extending its pulse width. This is useful for those applications where the 52 contacts
reporting the breaker state are faster than the 52 contacts that are responsible for
interrupting the coil current.
BLOCK RLY 1 TRIP
For details see
Common setpoints
.
This setting defines a block to the Trip Output relay. When the selected input is asserted,
the Trip Output relay will be blocked.
Output Relay 2 - W2
breaker "Trip"
PATH
:
SETPOINTS > S5 INPUTS/OUTPUTS > OUTPUT RELAYS > RLY 2 W2 BKRTRIP
RLY2 SEAL-IN
Range: 0.00 to 9.99 s in steps of 0.01
Default: 0.04 s
This setting defines the time to be added to the reset time of the Relay 2 Trip output,
thus extending its pulse width. This is useful for those applications where the 52 contacts
reporting the breaker state are faster than the 52 contacts that are responsible for
interrupting the coil current.
BLOCK RLY 2 TRIP
For details see
Common setpoints
.
This setting defines a block to the Close Output relay. When the selected input is
asserted, the Close Output relay will be blocked. The block function can be useful for
breaker maintenance purposes.