6–104
345 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL
S6 MONITORING
CHAPTER 6: SETPOINTS
•
Rolling Demand
: This selection calculates a linear average of the quantity (RMS
current, real power, reactive power, or apparent power) over the programmed
Demand time interval, in the same way as Block Interval. The value is updated every
minute and indicates the Demand over the time interval just proceeding the time of
update.
Current demand
The Current Demand for each phase is calculated individually, and the Demand for each
phase is monitored by comparison with a single Current Demand Pickup value. If the
Current Demand Pickup is equalled or exceeded by any phase, the relay can cause an
alarm or signal an output relay.
Path
:
S6 MONITORING > DEMAND > CURRENT DEMAND 1
Path
:
S6 MONITORING > DEMAND > CURRENT DEMAND 2
FUNCTION
Range: Disabled, Alarm, Latched Alarm
Default: Disabled
For details see
Common setpoints
.
CT INPUT
Range: CT (W1), CT (W2)
Default: CT (W1)
Select the current inputs from W1 CT, or W2 CT.
MEASUREMENT TYPE
Range: Blk Interval, Exponential, Rolling Dmd
Default: Blk Interval
This setting sets the measurement method. Three methods can be applied.
THERMAL 90% RESPONSE TIME
Range: 5 min, 10 min, 15 min, 20 min, 30 min
Default: 15 min
This setpoint sets the time required for a steady state current to indicate 90% of the
actual value and allows the user to approximately match the response of the relay to
analog instruments. The setpoint is visible only if MEASUREMENT TYPE is “Exponential”.
TIME INTERVAL
Range: 5 min, 10 min, 15 min, 20 min, 30 min
Default: 20 min
This setpoint sets the time period over which the current demand calculation is to be
performed. The setpoint is visible only if MEASUREMENT TYPE is “Block Interval” or
“Rolling Demand”.
PKP
Range: 10 to 10000 A in steps of 1 A
Default: 1000 A
This setpoint sets the Current Demand Pickup level.
OUTPUT RELAY X
For details see
Common setpoints
.
BLOCK
For details see
Common setpoints
.
Summary of Contents for 345
Page 89: ...CHAPTER 3 INTERFACES SOFTWARE SETUP 345 TRANSFORMER PROTECTION SYSTEM INSTRUCTION MANUAL 3 35 ...
Page 92: ...3 38 345 TRANSFORMER PROTECTION SYSTEM INSTRUCTION MANUAL SOFTWARE SETUP CHAPTER 3 INTERFACES ...
Page 254: ...A 8 345 TRANSFORMER PROTECTION SYSTEM INSTRUCTION MANUAL CHANGE NOTES ...