CHAPTER 6: SETPOINTS
S6 MONITORING
345 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL
6–109
THE RTD TROUBLE ALARM
All RTDs that are programmed with either an alarm or a trip are monitored for sensor
failure. When the measured temperature is greater than 250ºC or less than -50ºC, the RTD
is declared failed and a common RTD trouble alarm is issued.
RTD TROUBLE ALARM
Range: Disable, Enable
Default: Disable
This setting enables the RTD Trouble Alarm functionality.
OUTPUT RELAY X
For details see
Common setpoints
.
BLOCK 1 to 3
For details see
Common setpoints
.
Table 6-11: RTD Temperature vs Resistance
Temperature
100
Ω
Pt (DIN 43760)
o
C
o
F
–50
–58
80.31
–40
–40
84.27
–30
–22
88.22
–20
–4
92.16
–10
14
96.09
0
32
100.00
10
50
103.90
20
68
107.79
30
86
111.67
40
104
115.54
50
122
119.39
60
140
123.24
70
158
127.07
80
176
130.89
90
194
134.70
100
212
138.50
110
230
142.29
120
248
146.06
130
266
149.82
140
284
153.58
150
302
157.32
160
320
161.04
170
338
164.76
180
356
168.47
190
374
172.46
200
392
175.84
210
410
179.51
220
428
183.17
230
446
186.82
240
464
190.45
250
482
194.08