7–6
345 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL
M3 BREAKER MAINTENANCE
CHAPTER 7: MAINTENANCE
BYPASS BKR STATUS
Range: Disabled, Enabled
Default: Disabled
Set the “BYPASS BKR STATE” to Enabled when a by-pass resistor is connected across the
breaker auxiliary contact for continuous RLY1(2) circuit integrity monitoring. The circuits
will be monitored regardless of breaker position. When “BYPASS BKR STATE” is set to
Disabled, monitoring of the RLY1(2) coil will be blocked when the breaker is open.
OUTPUT RELAY X
Range: Do not operate, Operate
Default: Do not operate
For details see
Common setpoints
.