FEATURE INFORMATION
565/575 DATA FORMATS (REVISION E2.73)
FORMAT
APPLICABLE BITS
DEFINITION
CODE
0000 0000 0000 0011 (BIN) or 0003 (HEX)
03 (DEC) = SW. 3
0000 0000 0000 0100 (BIN) or 0004 (HEX)
04 (DEC) = SW. 4
0000 0000 0000 0101 (BIN) or 0005 (HEX)
05 (DEC) = SW. 5
0000 0000 0000 0110 (BIN) or 0006 (HEX)
06 (DEC) = SW. 6
0000 0000 0000 0111 (BIN) or 0007 (HEX)
07 (DEC) = SW. 7
0000 0000 0000 1000 (BIN) or 0008 (HEX)
08 (DEC) = SW. 8
F27
16 bits
PROGRAMMABLE SWITCH TRIP OPERATION MODE SELECTION
0000 0000 0000 0000 (BIN) or 0000 (HEX)
00 (DEC) = Non-Recl. (575)
0000 0000 0000 0001 (BIN) or 0001 (HEX)
01 (DEC) = Recl. (575)
F28
16 bits
EXTERNAL SWITCH CONFIGURATION/STATUS
0000 0000 0000 0000 (BIN) or 0000 (HEX)
00 (DEC) = Open
0000 0000 0000 0001 (BIN) or 0001 (HEX)
01 (DEC) = Closed
F29
16 bits
TRIP RELAY OPERATION MODE SELECTION
0000 0000 0000 0000 (BIN) or 0000 (HEX)
00 (DEC) = Latched (565)
0000 0000 0000 0001 (BIN) or 0001 (HEX)
01 (DEC) = Pulsed (565)
F30
16 bits
AUXILIARY RELAY OPERATION MODE SELECTION
0000 0000 0000 0000 (BIN) or 0000 (HEX)
00 (DEC) = Latched
0000 0000 0000 0001 (BIN) or 0001 (HEX)
01 (DEC) = Unlatched
0000 0000 0000 0010 (BIN) or 0002 (HEX)
02 (DEC) = Pulsed
F31
16 bits
EVENT PRINTING OPERATION MODE SELECTION
0000 0000 0000 0000 (BIN) or 0000 (HEX)
00 (DEC) = Offline
0000 0000 0000 0001 (BIN) or 0001 (HEX)
01 (DEC) = Online
F32
32 bits
ULONG (SPECIAL FOR ANALOG IN ALARM/TRIP THRESHOLDS)
XX XX 00 00 (HEX)
Lower Address Contains The Most Significant 16 bits
00 00 XX XX (HEX)
Upper Address Contains The Least Significant 16 bits
Example:
XXXXXX (DEC) * Scaling Factor = Result
Use The Following To Determine The Scaling Factor:
(1)
[(Maximum Current Scale Value - Minimum Current Scale Value) < 40.89] = 0.01
(2)
[(Maximum Current Scale Value - Minimum Current Scale Value) > 40.88]
And
[(Maximum Current Scale Value - Minimum Current Scale Value) < 408.80] = 0.1
(3)
[(Maximum Current Scale Value - Minimum Current Scale Value > 408.79)] = 1.0
Note: Only Reading The Upper Address Will Return Zero, As This Register Is Non-existent
F33
16 bits
ANALOG OUT PARAMETER SELECTION
0000 0000 0000 0000 (BIN) or 0000 (HEX)
00 (DEC) = Phase A Current
0000 0000 0000 0001 (BIN) or 0001 (HEX)
01 (DEC) = Phase B Current
0000 0000 0000 0010 (BIN) or 0002 (HEX)
02 (DEC) = Phase C Current
0000 0000 0000 0011 (BIN) or 0003 (HEX)
03 (DEC) = Ground Current
0000 0000 0000 0100 (BIN) or 0004 (HEX)
04 (DEC) = Phase A-X Voltage
0000 0000 0000 0101 (BIN) or 0005 (HEX)
05 (DEC) = Phase B-X Voltage
0000 0000 0000 0110 (BIN) or 0006 (HEX)
06 (DEC) = Phase C-X Voltage
0000 0000 0000 0111 (BIN) or 0007 (HEX)
07 (DEC) = Feeder Frequency
0000 0000 0000 1000 (BIN) or 0008 (HEX)
08 (DEC) = External Analog Select
F34
16 bits
ANALOG OUT RANGE SELECTION
0000 0000 0000 0000 (BIN) or 0000 (HEX)
00 (DEC) = 0 - 1 mA
0000 0000 0000 0001 (BIN) or 0001 (HEX)
01 (DEC) = 4 - 20 mA
F35
16 bits
COMMUNICATION BAUDRATE SELECTION
0000 0000 0000 0000 (BIN) or 0000 (HEX)
00 (DEC) = 1200 Baud
0000 0000 0000 0001 (BIN) or 0001 (HEX)
01 (DEC) = 2400 Baud
0000 0000 0000 0010 (BIN) or 0002 (HEX)
02 (DEC) = 4800 Baud
0000 0000 0000 0011 (BIN) or 0003 (HEX)
03 (DEC) = 9600 Baud
F36
16 bits
OUTPUT CONTACT TEST SELECTION
0000 0000 0000 0000 (BIN) or 0000 (HEX)
00 (DEC) = Trip
0000 0000 0000 0001 (BIN) or 0001 (HEX)
01 (DEC) = Aux 1
0000 0000 0000 0010 (BIN) or 0002 (HEX)
02 (DEC) = Aux 2
0000 0000 0000 0011 (BIN) or 0003 (HEX)
03 (DEC) = Aux 3
0000 0000 0000 0100 (BIN) or 0004 (HEX)
04 (DEC) = All (565), Aux 4 (575)
0000 0000 0000 0101 (BIN) or 0005 (HEX)
05 (DEC) = Block Tap Change (575)
0000 0000 0000 0110 (BIN) or 0006 (HEX)
06 (DEC) = All (575)
F37
16 bits
BREAKER OPEN/CLOSE STATUS
0000 0000 0000 0000 (BIN) or 0000 (HEX)
00 (DEC) = No
0000 0000 0000 0001 (BIN) or 0001 (HEX)
01 (DEC) = Yes
F38
16 bits
ANALOG SELECT STATUS
0000 0000 0000 0000 (BIN) or 0000 (HEX)
00 (DEC) = Off
0000 0000 0000 0001 (BIN) or 0001 (HEX)
01 (DEC) = On
F39
16 bits
LOCAL/REMOTE STATUS
0000 0000 0000 0000 (BIN) or 0000 (HEX)
00 (DEC) = Local
0000 0000 0000 0001 (BIN) or 0001 (HEX)
01 (DEC) = Remote
F40
16 bits
VT CONNECTION TYPE SELECTION
0000 0000 0000 0000 (BIN) or 0000 (HEX)
00 (DEC) = None
0000 0000 0000 0001 (BIN) or 0001 (HEX)
01 (DEC) = Wye
6-27
Summary of Contents for 565
Page 6: ...INSTALLATION 2 2 Figure 2 1 Mounting Details ...
Page 7: ...INSTALLATION 2 3 Figure 2 2 Mounting Arrangement with Relay Collar ...
Page 12: ...INSTALLATION 2 8 Figure 2 5 565 Relay Typical Wiring ...
Page 13: ...INSTALLATION 2 9 Figure 2 6 Voltage Sensing Wire ...
Page 14: ...INSTALLATION 2 10 Figure 2 7A 565 with MTM CT and Open Delta VT Typical Wiring ...
Page 15: ...INSTALLATION 2 11 Figure 2 7B 565 with MTM CT and Wye VT Typical Wiring ...
Page 16: ...INSTALLATION 2 12 Figure 2 8A Open Delta VT and CT MTM Typical Wiring ...
Page 17: ...INSTALLATION 2 13 Figure 2 8B Wye VT and CT MTM Typical Wiring ...
Page 18: ...INSTALLATION 2 14 Figure 2 9 MTM Mounting Dimensions ...
Page 19: ...INSTALLATION 2 15 Figure 2 10 565 Rear Panel Layout ...
Page 20: ......
Page 23: ...DISPLAY AND KEYBOARD 3 3 Figure 4 1 565 Relay Front Panel ...
Page 28: ......
Page 132: ......
Page 142: ...CURVE INFORMATION ANDTABLES 7 10 Figure 7 9 IEC A Curves ...
Page 143: ...CURVE INFORMATION ANDTABLES 7 11 Figure 7 10 IEC B Curves ...
Page 144: ...CURVE INFORMATION ANDTABLES 7 12 Figure 7 11 IEC C Curves ...
Page 176: ...RELAYTESTING 8 2 Figure 8 1 Secondary Injection Test Setup ...
Page 180: ......
Page 184: ......
Page 192: ...APPENDIX C C 2 Figure C1 System Controller Block Diagram 1 2 ...
Page 193: ...APPENDIX C C 3 Figure C2 System Controller Block Diagram 2 2 ...
Page 194: ......
Page 198: ......