SETPOINTS MODE
5-8
Analog In Alarm
12.00.
Min Curr Scale Value to Max Curr Scale Value
Analog In Alarm Delay
1 Sec.
1 to 255 sec
1 sec
Analog In Alarm Relay
Aux1. (Aux2 for 575)
Aux1, Aux2, Aux1&2 (575: None, Aux1, Aux2, Aux1&2)
6. Analog Output setpoints.
Analog Output Parameter
Phase A Current.
Phase A Current, Phase B Current, Phase C Current,
Ground Current, Phase A-X Voltage, Phase B-X Voltage,
Phase C-X Voltage, Feeder Frequency, and External
Analog Select
Analog Output Range:
4-20 mA.
0-1mA or 4-20mA
7. Communication setpoints.
Relay Address
1.
1 to 254
1
Baud Rate
2400 BAUD.
1200, 2400, 4800, and 9600 Baud
8. Calibration Mode setpoints.
Exercise Relay
Trip.
Trip, Aux1, Aux2, Aux3, and All (565)
Trip, Aux1, Aux2, Aux3, Aux4, Block Tap Changer, and
All (575)
(Status of Switch Inputs)
LCD Display Contrast
5.
0 to 10
1
9. Voltage setpoints.
VT Connection
Wye.
Wye, Open Delta, Delta/Wye and None
VT Nominal Sec Volts
120 Volts.
48 to 240 Volts
VT Primary Volts
1.2 kV.
0.1 to 69 kV
0.01 kV
Zero Volts Detect
Disabled.
Enabled/Disabled
Undervolt Trip
Disabled.
Enabled/Disabled
Undervolt Trip Level
80% VT
50 to 100%
1%
Undervolt Trip Delay
1.0 Sec.
0.1 to 25.5 sec
0.1 sec
Undervolt Trip Relay
Trip & Aux1.
Trip, Aux1, Aux2, Trip&Aux1, Trip&Aux2, Aux1&2, and
Trip&Aux1&2 (575: Trip, Trip&Aux1, Aux2)
Undervolt Alarm
Disabled.
Enabled/Disabled
Undervolt Alarm Level
85% VT
50 to 100%
1%
Undervolt Alarm Delay
1.0 Sec.
0.1 to 25.5 sec
0.1 sec
Undervolt Alarm Relay
Aux2.
Aux1, Aux2, and Aux1&2 (575: None, Aux1, Aux2,
Aux1&2)
Overvolt Trip
Disabled.
Enabled/Disabled
Overvolt Trip Level
120% VT
101 to 125%
1%
Overvolt Trip Delay
1.0 Sec.
0.1 to 25.5 sec
0.1 sec
Overvolt Trip Relay
Trip. (Trip&Aux1 for 575)
Trip, Aux1, Aux2, Trip&Aux1, Trip&Aux2, Aux1&2, and
Trip&Aux1&2 (575: Trip, Trip&Aux1, Aux2)
Overvolt Alarm
Disabled.
Enabled/Disabled
Overvolt Alarm Level
115% VT
101 to 125%
1%
Overvolt Alarm Delay
1.0 Sec.
0.1 to 25.5 sec
0.1 sec
Overvolt Alarm Relay
Aux1. (Aux2 for 575)
Aux1, Aux2, Aux1&2 (575: None, Aux1, Aux2, Aux1&2)
10. Demand Metering setpoints.
Amps Demand
Enabled.
Enabled/Disabled
Amps Demand Time Period
5 Min.
5 to 120 Min
1 Min
Amps Demand Alarm
Disabled.
Enabled/Disabled
Amp Demand Alarm Level
100 A.
10 to 5000 A
5 A
Setpoint Name
Factory Setpoint
Range
Step
Summary of Contents for 565
Page 6: ...INSTALLATION 2 2 Figure 2 1 Mounting Details ...
Page 7: ...INSTALLATION 2 3 Figure 2 2 Mounting Arrangement with Relay Collar ...
Page 12: ...INSTALLATION 2 8 Figure 2 5 565 Relay Typical Wiring ...
Page 13: ...INSTALLATION 2 9 Figure 2 6 Voltage Sensing Wire ...
Page 14: ...INSTALLATION 2 10 Figure 2 7A 565 with MTM CT and Open Delta VT Typical Wiring ...
Page 15: ...INSTALLATION 2 11 Figure 2 7B 565 with MTM CT and Wye VT Typical Wiring ...
Page 16: ...INSTALLATION 2 12 Figure 2 8A Open Delta VT and CT MTM Typical Wiring ...
Page 17: ...INSTALLATION 2 13 Figure 2 8B Wye VT and CT MTM Typical Wiring ...
Page 18: ...INSTALLATION 2 14 Figure 2 9 MTM Mounting Dimensions ...
Page 19: ...INSTALLATION 2 15 Figure 2 10 565 Rear Panel Layout ...
Page 20: ......
Page 23: ...DISPLAY AND KEYBOARD 3 3 Figure 4 1 565 Relay Front Panel ...
Page 28: ......
Page 132: ......
Page 142: ...CURVE INFORMATION ANDTABLES 7 10 Figure 7 9 IEC A Curves ...
Page 143: ...CURVE INFORMATION ANDTABLES 7 11 Figure 7 10 IEC B Curves ...
Page 144: ...CURVE INFORMATION ANDTABLES 7 12 Figure 7 11 IEC C Curves ...
Page 176: ...RELAYTESTING 8 2 Figure 8 1 Secondary Injection Test Setup ...
Page 180: ......
Page 184: ......
Page 192: ...APPENDIX C C 2 Figure C1 System Controller Block Diagram 1 2 ...
Page 193: ...APPENDIX C C 3 Figure C2 System Controller Block Diagram 2 2 ...
Page 194: ......
Page 198: ......