5-14
Location
Message Line
Description
S 2.1
SETPOINTS
PHASE CURRENT
The setpoints page 2 header. In this page you must enter information
about the phase current transformers being used in your application. This
allows the 565/575 Relay to accurately sense the feeder currents. This
page also allows you to set the levels for various overcurrent alarms and
trips and assign relays to be activated by these.
Each of the four phase currents are sampled at a rate of approximately 960 samples per second.
S 2.2
PHASE CT RATING
PRIMARY 100 A
Enter the primary current rating of the phase current transformers being
used. This value is found on the transformer nameplate. Values can be
entered in the range of 10 to 5000 Amps, in steps of 5 Amp. If an attempt
is made to enter a value outside this range an OUT OF RANGE error
message will flash. If your transformer has a rating outside this range
contact MULTILIN for information. Note that all three phase CT’s must
have the same rating.
S 2.3
PHASE TIMED O/C
PICKUP 100 %CT
The phase overcurrent pickup level is entered here. This is given as a
percentage of the CT rating, in the range of 25% to 250% in steps of 1%.
This setting will determine the level of current which the 565 Relay will
identify as too high, and then initiate a timed overcurrent trip of the
breaker, according to the selected curve shape.
For example, if 50% is entered here, then the 565/575 Relay will initiate a
timed trip of the feeder breaker when at least one of the phase currents
reaches 50% of the full CT rating entered in message S 2.2. Determine this
value by referring to the feeder design specifications.
S 2.4
PHASE O/C CURVE
SHAPE EXTREM INV
The shape of the required protection curve must be entered here. The
curve names are shown below together with the shortened form of the
name which is displayed in this message.
CURVE
DISPLAYED
NAME
NAME
1. Moderately inverse.
MOD INV.
2. Normal Inverse.
NORMAL INV.
3. Very Inverse.
VERY INV.
4. Extremely Inverse.
EXTREM INV.
5. Custom Curve.
CUSTOM
6. IEC
IEC A
7. IEC
IEC B
8. IEC
IEC C
Once the correct curve has been chosen for your application, press the
NEXT CHOICE key until the required curve is displayed in message S 2.4
and store the selected curve using the STORE key. The extremely inverse
curve is shown in this example.
Message S 2.5 will not appear if CUSTOM CURVE is selected in message S 2.4.
S 2.5
PHASE O/C
TIME DIAL 1
The phase overcurrent time dial number is entered here. This allows the
user to fit the selected curve to the system requirements. Any of the 32
possible plots of the selected curve shape may be selected by entering the
corresponding number between 1 and 32 here. Select the curve number
by referring to the “use of standard curves” in section 3.
S 2.6
PHASE O/C TRIP
RELAY TRIP
This message allows the user to select the relay which the phase overcur-
rent trip will activate.
SETPOINTS MODE - PHASE CURRENT
Summary of Contents for 565
Page 6: ...INSTALLATION 2 2 Figure 2 1 Mounting Details ...
Page 7: ...INSTALLATION 2 3 Figure 2 2 Mounting Arrangement with Relay Collar ...
Page 12: ...INSTALLATION 2 8 Figure 2 5 565 Relay Typical Wiring ...
Page 13: ...INSTALLATION 2 9 Figure 2 6 Voltage Sensing Wire ...
Page 14: ...INSTALLATION 2 10 Figure 2 7A 565 with MTM CT and Open Delta VT Typical Wiring ...
Page 15: ...INSTALLATION 2 11 Figure 2 7B 565 with MTM CT and Wye VT Typical Wiring ...
Page 16: ...INSTALLATION 2 12 Figure 2 8A Open Delta VT and CT MTM Typical Wiring ...
Page 17: ...INSTALLATION 2 13 Figure 2 8B Wye VT and CT MTM Typical Wiring ...
Page 18: ...INSTALLATION 2 14 Figure 2 9 MTM Mounting Dimensions ...
Page 19: ...INSTALLATION 2 15 Figure 2 10 565 Rear Panel Layout ...
Page 20: ......
Page 23: ...DISPLAY AND KEYBOARD 3 3 Figure 4 1 565 Relay Front Panel ...
Page 28: ......
Page 132: ......
Page 142: ...CURVE INFORMATION ANDTABLES 7 10 Figure 7 9 IEC A Curves ...
Page 143: ...CURVE INFORMATION ANDTABLES 7 11 Figure 7 10 IEC B Curves ...
Page 144: ...CURVE INFORMATION ANDTABLES 7 12 Figure 7 11 IEC C Curves ...
Page 176: ...RELAYTESTING 8 2 Figure 8 1 Secondary Injection Test Setup ...
Page 180: ......
Page 184: ......
Page 192: ...APPENDIX C C 2 Figure C1 System Controller Block Diagram 1 2 ...
Page 193: ...APPENDIX C C 3 Figure C2 System Controller Block Diagram 2 2 ...
Page 194: ......
Page 198: ......