5-28
Location
Message Line
Description
CONDITION
OUTPUT
AUX. 1 RELAY
FACEPLATE
AUX. 1 LED
MODBUS READ EXCEPTION
STATUS
NO ALARM
DE-ENERGIZED
OFF
00H
ALARM
(Alarm Level < Curr. < P/U)
(Brkr. Open)
PULSES
ON
40H
ALARM
(Curr. > Alarm & P/U Level)
ENERGIZED
OFF
40H
ALARM
(Curr. < Alarm & P/U Level)
(Brkr. Open)
DE-ENERGIZED
OFF
00H
KEYPAD RESET
DE-ENERGIZED
OFF
00H
Latched
If latched operation is chosen for the Aux 1 relay, it will energize when a
trip/alarm occurs. Pressing the RESET key on the front panel will unlatch
the Aux 1 relay only if the fault current is below the trip/alarm level. This
may be convenient if the relay is being used to annunciate a fault condition.
When programmed as latched, the Aux 1 relay does not look at the 52a/
52b contacts.
CONDITION
OUTPUT AUX. 1
RELAY
FACEPLATE
AUX. 1 LED
MODBUS READ EXCEPTION
STATUS
NO TRIP
DE-ENERGIZED
OFF
00H
TRIPPED
(Current > Trip Level)
ENERGIZED
ON
44H
TRIPPED
(Current < Trip Level)
ENERGIZED
ON
44H
KEYPAD RESET
DE-ENERGIZED
OFF
00H
CONDITION
OUTPUT AUX. 1
RELAY
FACEPLATE
AUX. 1 LED
MODBUS READ EXCEPTION
STATUS
NO ALARM
DE-ENERGIZED
OFF
00H
ALARM
(Current > Alarm Level)
ENERGIZED
ON
40H
ALARM
(Current < Alarm Level)
ENERGIZED
ON
40H
KEYPAD RESET
DE-ENERGIZED
OFF
00H
Unlatched
If unlatched operation is selected, the Aux 1 relay becomes energized
upon declaration of a fault/ alarm condition. When current drops below the
alarm/trip level, the relay will de-energize. When programmed as un-
latched, the Aux 1 relay does not look at the 52a/52b contacts.
SETPOINTS MODE - CONFIGURATION
Summary of Contents for 565
Page 6: ...INSTALLATION 2 2 Figure 2 1 Mounting Details ...
Page 7: ...INSTALLATION 2 3 Figure 2 2 Mounting Arrangement with Relay Collar ...
Page 12: ...INSTALLATION 2 8 Figure 2 5 565 Relay Typical Wiring ...
Page 13: ...INSTALLATION 2 9 Figure 2 6 Voltage Sensing Wire ...
Page 14: ...INSTALLATION 2 10 Figure 2 7A 565 with MTM CT and Open Delta VT Typical Wiring ...
Page 15: ...INSTALLATION 2 11 Figure 2 7B 565 with MTM CT and Wye VT Typical Wiring ...
Page 16: ...INSTALLATION 2 12 Figure 2 8A Open Delta VT and CT MTM Typical Wiring ...
Page 17: ...INSTALLATION 2 13 Figure 2 8B Wye VT and CT MTM Typical Wiring ...
Page 18: ...INSTALLATION 2 14 Figure 2 9 MTM Mounting Dimensions ...
Page 19: ...INSTALLATION 2 15 Figure 2 10 565 Rear Panel Layout ...
Page 20: ......
Page 23: ...DISPLAY AND KEYBOARD 3 3 Figure 4 1 565 Relay Front Panel ...
Page 28: ......
Page 132: ......
Page 142: ...CURVE INFORMATION ANDTABLES 7 10 Figure 7 9 IEC A Curves ...
Page 143: ...CURVE INFORMATION ANDTABLES 7 11 Figure 7 10 IEC B Curves ...
Page 144: ...CURVE INFORMATION ANDTABLES 7 12 Figure 7 11 IEC C Curves ...
Page 176: ...RELAYTESTING 8 2 Figure 8 1 Secondary Injection Test Setup ...
Page 180: ......
Page 184: ......
Page 192: ...APPENDIX C C 2 Figure C1 System Controller Block Diagram 1 2 ...
Page 193: ...APPENDIX C C 3 Figure C2 System Controller Block Diagram 2 2 ...
Page 194: ......
Page 198: ......