5-39
Location
Message Line
Description
S 8.1
SETPOINTS
CALIBRATION MODE
The setpoints page 8 header. This page is used to test the operation of the
565 switch inputs and output relays. As well, the LCD display contrast can
be adjusted on this page.
S 8.2
EXERCISE RELAY
TRIP
This message is used to test the operation of the output relay contacts.
The following choices are available:
1) Trip.
4) Aux. 3.
7) ALL
2) Aux. 1.
5) Aux. 4 (575 only)
3) Aux. 2.
6) Block Tap Changer (575 only)
Select the required relay using the NEXT CHOICE key. Press the store key
to simulate the presence of a condition that will activate the selected relay.
Before testing, verify that it is safe to do so. (These tests can only be done with the feeder breaker open.) If the breaker
is closed, the following flash message will be displayed:
BREAKER MUST
BE OPEN
S 8.3
PRESS STORE
TO END TEST...
This message appears while the activating condition is present. The relay
will be tested in the mode of operation assigned to it. For example, a
latched relay will be energized and will then remain latched. Press the
STORE key to remove the simulated activating condition.
S 8.4
PRESS RESET TO
RESET RELAY
This message appears on the display for two seconds to remind the user
that if a latched relay has been tested, then the reset key must now be
pressed to return the relay to its inactive state.
S 8.5
SWITCH NUMBER 1
STATUS OPEN
This message allows each of the external switches to have its status
checked. Use the LINE DOWN key to display each of the switches. The
status of each switch, either OPEN or CLOSED will appear in the mes-
sage.
S 8.6
BREAKER OPEN
STATUS YES
This message allows the breaker open external contacts to have their
status checked.
S 8.7
BREAKER CLOSED
STATUS NO
This message allows the breaker closed external contacts to have their
status checked.
S 8.8
ANALOG SELECT A
STATUS OFF
This message allows each of the analog select switches to have its status
checked. Use the LINE DOWN key to display each of the switches. The
status of each switch, either ON or OFF, will appear in the messages.
S 8.9
ACCESS JUMPER
STATUS ENABLED
This message indicates the status of the access jumper. ENABLED
indicates jumper installed. DISABLED indicates jumper not installed.
S 8.10
REMOTE/LOCAL 43
STATUS LOCAL
S 8.11
RECLOSE ENABLED
STATUS YES
This message indicates the status of the internal hardware relay which
enables or disables the reclosing scheme.
L
A
L
A
L
A
L
A
L
A
L
A
L
A
L
A
SETPOINTS MODE - CALIBRATION
Summary of Contents for 565
Page 6: ...INSTALLATION 2 2 Figure 2 1 Mounting Details ...
Page 7: ...INSTALLATION 2 3 Figure 2 2 Mounting Arrangement with Relay Collar ...
Page 12: ...INSTALLATION 2 8 Figure 2 5 565 Relay Typical Wiring ...
Page 13: ...INSTALLATION 2 9 Figure 2 6 Voltage Sensing Wire ...
Page 14: ...INSTALLATION 2 10 Figure 2 7A 565 with MTM CT and Open Delta VT Typical Wiring ...
Page 15: ...INSTALLATION 2 11 Figure 2 7B 565 with MTM CT and Wye VT Typical Wiring ...
Page 16: ...INSTALLATION 2 12 Figure 2 8A Open Delta VT and CT MTM Typical Wiring ...
Page 17: ...INSTALLATION 2 13 Figure 2 8B Wye VT and CT MTM Typical Wiring ...
Page 18: ...INSTALLATION 2 14 Figure 2 9 MTM Mounting Dimensions ...
Page 19: ...INSTALLATION 2 15 Figure 2 10 565 Rear Panel Layout ...
Page 20: ......
Page 23: ...DISPLAY AND KEYBOARD 3 3 Figure 4 1 565 Relay Front Panel ...
Page 28: ......
Page 132: ......
Page 142: ...CURVE INFORMATION ANDTABLES 7 10 Figure 7 9 IEC A Curves ...
Page 143: ...CURVE INFORMATION ANDTABLES 7 11 Figure 7 10 IEC B Curves ...
Page 144: ...CURVE INFORMATION ANDTABLES 7 12 Figure 7 11 IEC C Curves ...
Page 176: ...RELAYTESTING 8 2 Figure 8 1 Secondary Injection Test Setup ...
Page 180: ......
Page 184: ......
Page 192: ...APPENDIX C C 2 Figure C1 System Controller Block Diagram 1 2 ...
Page 193: ...APPENDIX C C 3 Figure C2 System Controller Block Diagram 2 2 ...
Page 194: ......
Page 198: ......