GE Multilin
C60 Breaker Protection System
5-49
5 SETTINGS
5.2 PRODUCT SETUP
5
5.2.13 CONTROL PUSHBUTTONS
PATH: SETTINGS
Ö
PRODUCT SETUP
ÖØ
CONTROL PUSHBUTTONS
Ö
CONTROL PUSHBUTTON 1(7)
There are three standard control pushbuttons, labeled USER 1, USER 2, and USER 3, on the standard and enhanced front
panels. These are user-programmable and can be used for various applications such as performing an LED test, switching
setting groups, and invoking and scrolling though user-programmable displays.
Firmware revisions 3.2x and older use these three pushbuttons for manual breaker control. This functionality has been
retained – if the breaker control feature is configured to use the three pushbuttons, they cannot be used as user-program-
mable control pushbuttons.
The location of the control pushbuttons are shown in the following figures.
Figure 5–5: CONTROL PUSHBUTTONS (ENHANCED FACEPLATE)
An additional four control pushbuttons are included on the standard faceplate when the C60 is ordered with the twelve
user-programmable pushbutton option.
Figure 5–6: CONTROL PUSHBUTTONS (STANDARD FACEPLATE)
Control pushbuttons are not typically used for critical operations and are not protected by the control password. However,
by supervising their output operands, the user can dynamically enable or disable control pushbuttons for security reasons.
Each control pushbutton asserts its own FlexLogic™ operand. These operands should be configured appropriately to per-
form the desired function. The operand remains asserted as long as the pushbutton is pressed and resets when the push-
button is released. A dropout delay of 100 ms is incorporated to ensure fast pushbutton manipulation will be recognized by
various features that may use control pushbuttons as inputs.
An event is logged in the event record (as per user setting) when a control pushbutton is pressed. No event is logged when
the pushbutton is released. The faceplate keys (including control keys) cannot be operated simultaneously – a given key
must be released before the next one can be pressed.
CONTROL
PUSHBUTTON 1
CONTROL PUSHBUTTON 1
FUNCTION: Disabled
Range: Disabled, Enabled
MESSAGE
CONTROL PUSHBUTTON 1
EVENTS: Disabled
Range: Disabled, Enabled
Control pushbuttons
842813A1.CDR
842733A2.CDR
PICKUP
ALARM
TRIP
TEST MODE
TROUBLE
IN SERVICE
STATUS
USER 3
USER 2
USER 1
RESET
EVENT CAUSE
NEUTRAL/GROUND
PHASE C
PHASE B
PHASE A
OTHER
FREQUENCY
CURRENT
VOLTAGE
THREE
STANDARD
CONTROL
PUSHBUTTONS
USER 7
USER 6
USER 5
USER 4
FOUR EXTRA
OPTIONAL
CONTROL
PUSHBUTTONS
Summary of Contents for C60 UR series
Page 2: ......
Page 4: ......
Page 11: ...GE Multilin C60 Breaker Protection System xi TABLE OF CONTENTS INDEX...
Page 12: ...xii C60 Breaker Protection System GE Multilin TABLE OF CONTENTS...
Page 32: ...1 20 C60 Breaker Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1...
Page 50: ...2 18 C60 Breaker Protection System GE Multilin 2 2 SPECIFICATIONS 2 PRODUCT DESCRIPTION 2...
Page 128: ...4 30 C60 Breaker Protection System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4...
Page 394: ...9 4 C60 Breaker Protection System GE Multilin 9 1 FAULT LOCATOR 9 THEORY OF OPERATION 9...
Page 516: ...D 10 C60 Breaker Protection System GE Multilin D 1 OVERVIEW APPENDIXD D...
Page 528: ...E 12 C60 Breaker Protection System GE Multilin E 2 DNP POINT LISTS APPENDIXE E...