GE Multilin
C60 Breaker Protection System
5-75
5 SETTINGS
5.4 SYSTEM SETUP
5
5.4.4 BREAKERS
PATH: SETTINGS
ÖØ
SYSTEM SETUP
ÖØ
BREAKERS
Ö
BREAKER 1(4)
BREAKER 1
BREAKER 1
FUNCTION: Disabled
Range: Disabled, Enabled
MESSAGE
BREAKER1 PUSH BUTTON
CONTROL: Disabled
Range: Disabled, Enabled
MESSAGE
BREAKER 1 NAME:
Bkr 1
Range: up to 6 alphanumeric characters
MESSAGE
BREAKER 1 MODE:
3-Pole
Range: 3-Pole, 1-Pole
MESSAGE
BREAKER 1 OPEN:
Off
Range: FlexLogic™ operand
MESSAGE
BREAKER 1 BLK OPEN:
Off
Range: FlexLogic™ operand
MESSAGE
BREAKER 1 CLOSE:
Off
Range: FlexLogic™ operand
MESSAGE
BREAKER 1 BLK CLOSE:
Off
Range: FlexLogic™ operand
MESSAGE
BREAKER 1
Φ
A/3P CLSD:
Off
Range: FlexLogic™ operand
MESSAGE
BREAKER 1
Φ
A/3P OPND:
Off
Range: FlexLogic™ operand
MESSAGE
BREAKER 1
Φ
B CLOSED:
Off
Range: FlexLogic™ operand
MESSAGE
BREAKER 1
Φ
B OPENED:
Off
Range: FlexLogic™ operand
MESSAGE
BREAKER 1
Φ
C CLOSED:
Off
Range: FlexLogic™ operand
MESSAGE
BREAKER 1
Φ
C OPENED:
Off
Range: FlexLogic™ operand
MESSAGE
BREAKER 1 Toperate:
0.070 s
Range: 0.000 to 2.000 s in steps of 0.001
MESSAGE
BREAKER 1 EXT ALARM:
Off
Range: FlexLogic™ operand
MESSAGE
BREAKER 1 ALARM
DELAY: 0.000
s
Range: 0.000 to 1 000 000.000 s in steps of 0.001
MESSAGE
MANUAL CLOSE RECAL1
TIME: 0.000
s
Range: 0.000 to 1 000 000.000 s in steps of 0.001
MESSAGE
BREAKER 1 OUT OF SV:
Off
Range: FlexLogic™ operand
MESSAGE
BREAKER 1 EVENTS:
Disabled
Range: Disabled, Enabled
Summary of Contents for C60 UR series
Page 2: ......
Page 4: ......
Page 11: ...GE Multilin C60 Breaker Protection System xi TABLE OF CONTENTS INDEX...
Page 12: ...xii C60 Breaker Protection System GE Multilin TABLE OF CONTENTS...
Page 32: ...1 20 C60 Breaker Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1...
Page 50: ...2 18 C60 Breaker Protection System GE Multilin 2 2 SPECIFICATIONS 2 PRODUCT DESCRIPTION 2...
Page 128: ...4 30 C60 Breaker Protection System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4...
Page 394: ...9 4 C60 Breaker Protection System GE Multilin 9 1 FAULT LOCATOR 9 THEORY OF OPERATION 9...
Page 516: ...D 10 C60 Breaker Protection System GE Multilin D 1 OVERVIEW APPENDIXD D...
Page 528: ...E 12 C60 Breaker Protection System GE Multilin E 2 DNP POINT LISTS APPENDIXE E...