g
GE Industrial Systems
ADDENDUM
This addendum contains information that relates to the C60 Breaker Protection System, version 5.7x. This addendum
lists a number of information items that appear in the instruction manual GEK-113516 (revision
U1
) but are not included
in the current C60 operations.
The following functions and items are not yet available with the current version of the C60 relay:
• Signal sources SRC 5 and SRC 6.
Version 4.0x and higher releases of the C60 relay includes new hardware (CPU and CT/VT modules).
• The new CPU modules are specified with the following order codes: 9E, 9G, 9H, 9J, 9K, 9L, 9M, 9N, 9P, 9R, and 9S.
• The new CT/VT modules are specified with the following order codes: 8F, 8G, 8H, 8J 8L, 8M, 8N, 8R.
The following table maps the relationship between the old CPU and CT/VT modules to the newer versions:
The new CT/VT modules can only be used with the new CPUs (9E, 9G, 9H, 9J, 9K, 9L, 9M, 9N, 9P, 9R, and 9S), and
the old CT/VT modules can only be used with the old CPU modules (9A, 9C, 9D). To prevent any hardware mis-
matches, the new CPU and CT/VT modules have blue labels and a warning sticker stating
“Attn.: Ensure CPU and
DSP module label colors are the same!”
. In the event that there is a mismatch between the CPU and CT/VT module,
the relay will not function and a
DSP ERROR
or
HARDWARE MISMATCH
error will be displayed.
All other input/output modules are compatible with the new hardware.
With respect to the firmware, firmware versions 4.0x and higher are only compatible with the new CPU and CT/VT mod-
ules. Previous versions of the firmware (3.4x and earlier) are only compatible with the older CPU and CT/VT modules.
MODULE
OLD
NEW
DESCRIPTION
CPU
9A
9E
RS485 and RS485 (Modbus RTU, DNP)
9C
9G
RS485 and 10Base-F (Ethernet, Modbus TCP/IP, DNP)
9D
9H
RS485 and redundant 10Base-F (Ethernet, Modbus TCP/IP, DNP)
---
9J
RS485 and multi-mode ST 100Base-FX
---
9K
RS485 and multi-mode ST redundant 100Base-FX
---
9L
RS485 and single mode SC 100Base-FX
---
9M
RS485 and single mode SC redundant 100Base-FX
---
9N
RS485 and 10/100Base-T
---
9P
RS485 and single mode ST 100Base-FX
---
9R
RS485 and single mode ST redundant 100Base-FX
---
9S
RS485 and six-port managed Ethernet switch
CT/VT
8A
8F
Standard 4CT/4VT
8B
8G
Sensitive ground 4CT/4VT
8C
8H
Standard 8CT
8D
8J
Sensitive ground 8CT
--
8L
Standard 4CT/4VT with enhanced diagnostics
--
8M
Sensitive ground 4CT/4VT with enhanced diagnostics
--
8N
Standard 8CT with enhanced diagnostics
--
8R
Sensitive ground 8CT with enhanced diagnostics
Addendum
Summary of Contents for C60 UR series
Page 2: ......
Page 4: ......
Page 11: ...GE Multilin C60 Breaker Protection System xi TABLE OF CONTENTS INDEX...
Page 12: ...xii C60 Breaker Protection System GE Multilin TABLE OF CONTENTS...
Page 32: ...1 20 C60 Breaker Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1...
Page 50: ...2 18 C60 Breaker Protection System GE Multilin 2 2 SPECIFICATIONS 2 PRODUCT DESCRIPTION 2...
Page 128: ...4 30 C60 Breaker Protection System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4...
Page 394: ...9 4 C60 Breaker Protection System GE Multilin 9 1 FAULT LOCATOR 9 THEORY OF OPERATION 9...
Page 516: ...D 10 C60 Breaker Protection System GE Multilin D 1 OVERVIEW APPENDIXD D...
Page 528: ...E 12 C60 Breaker Protection System GE Multilin E 2 DNP POINT LISTS APPENDIXE E...