GE Multilin
C60 Breaker Protection System
B-11
APPENDIX B
B.4 MEMORY MAPPING
B
1808
Source 1 Phase A Current Magnitude
0 to 999999.999
A
0.001
F060
0
180A
Source 1 Phase A Current Angle
-359.9 to 0
degrees
0.1
F002
0
180B
Source 1 Phase B Current Magnitude
0 to 999999.999
A
0.001
F060
0
180D
Source 1 Phase B Current Angle
-359.9 to 0
degrees
0.1
F002
0
180E
Source 1 Phase C Current Magnitude
0 to 999999.999
A
0.001
F060
0
1810
Source 1 Phase C Current Angle
-359.9 to 0
degrees
0.1
F002
0
1811
Source 1 Neutral Current Magnitude
0 to 999999.999
A
0.001
F060
0
1813
Source 1 Neutral Current Angle
-359.9 to 0
degrees
0.1
F002
0
1814
Source 1 Ground Current RMS
0 to 999999.999
A
0.001
F060
0
1816
Source 1 Ground Current Magnitude
0 to 999999.999
A
0.001
F060
0
1818
Source 1 Ground Current Angle
-359.9 to 0
degrees
0.1
F002
0
1819
Source 1 Zero Sequence Current Magnitude
0 to 999999.999
A
0.001
F060
0
181B
Source 1 Zero Sequence Current Angle
-359.9 to 0
degrees
0.1
F002
0
181C
Source 1 Positive Sequence Current Magnitude
0 to 999999.999
A
0.001
F060
0
181E
Source 1 Positive Sequence Current Angle
-359.9 to 0
degrees
0.1
F002
0
181F
Source 1 Negative Sequence Current Magnitude
0 to 999999.999
A
0.001
F060
0
1821
Source 1 Negative Sequence Current Angle
-359.9 to 0
degrees
0.1
F002
0
1822
Source 1 Differential Ground Current Magnitude
0 to 999999.999
A
0.001
F060
0
1824
Source 1 Differential Ground Current Angle
-359.9 to 0
degrees
0.1
F002
0
1825
Reserved (27 items)
---
---
---
F001
0
1840
...Repeated for Source 2
1880
...Repeated for Source 3
18C0
...Repeated for Source 4
1900
...Repeated for Source 5
1940
...Repeated for Source 6
Source Voltage (Read Only) (6 modules)
1A00
Source 1 Phase AG Voltage RMS
V
F060
0
1A02
Source 1 Phase BG Voltage RMS
V
F060
0
1A04
Source 1 Phase CG Voltage RMS
V
F060
0
1A06
Source 1 Phase AG Voltage Magnitude
0 to 999999.999
V
0.001
F060
0
1A08
Source 1 Phase AG Voltage Angle
-359.9 to 0
degrees
0.1
F002
0
1A09
Source 1 Phase BG Voltage Magnitude
0 to 999999.999
V
0.001
F060
0
1A0B
Source 1 Phase BG Voltage Angle
-359.9 to 0
degrees
0.1
F002
0
1A0C
Source 1 Phase CG Voltage Magnitude
0 to 999999.999
V
0.001
F060
0
1A0E
Source 1 Phase CG Voltage Angle
-359.9 to 0
degrees
0.1
F002
0
1A0F
Source 1 Phase AB or AC Voltage RMS
0 to 999999.999
V
0.001
F060
0
1A11
Source 1 Phase BC or BA Voltage RMS
0 to 999999.999
V
0.001
F060
0
1A13
Source 1 Phase CA or CB Voltage RMS
0 to 999999.999
V
0.001
F060
0
1A15
Source 1 Phase AB or AC Voltage Magnitude
0 to 999999.999
V
0.001
F060
0
1A17
Source 1 Phase AB or AC Voltage Angle
-359.9 to 0
degrees
0.1
F002
0
1A18
Source 1 Phase BC or BA Voltage Magnitude
0 to 999999.999
V
0.001
F060
0
1A1A
Source 1 Phase BC or BA Voltage Angle
-359.9 to 0
degrees
0.1
F002
0
1A1B
Source 1 Phase CA or CB Voltage Magnitude
0 to 999999.999
V
0.001
F060
0
1A1D
Source 1 Phase CA or CB Voltage Angle
-359.9 to 0
degrees
0.1
F002
0
1A1E
Source 1 Auxiliary Voltage RMS
V
F060
0
1A20
Source 1 Auxiliary Voltage Magnitude
0 to 999999.999
V
0.001
F060
0
1A22
Source 1 Auxiliary Voltage Angle
-359.9 to 0
degrees
0.1
F002
0
1A23
Source 1 Zero Sequence Voltage Magnitude
0 to 999999.999
V
0.001
F060
0
1A25
Source 1 Zero Sequence Voltage Angle
-359.9 to 0
degrees
0.1
F002
0
1A26
Source 1 Positive Sequence Voltage Magnitude
0 to 999999.999
V
0.001
F060
0
1A28
Source 1 Positive Sequence Voltage Angle
-359.9 to 0
degrees
0.1
F002
0
1A29
Source 1 Negative Sequence Voltage Magnitude
0 to 999999.999
V
0.001
F060
0
1A2B
Source 1 Negative Sequence Voltage Angle
-359.9 to 0
degrees
0.1
F002
0
1A2C
Reserved (20 items)
---
---
---
F001
0
Table B–9: MODBUS MEMORY MAP (Sheet 4 of 50)
ADDR
REGISTER NAME
RANGE
UNITS
STEP
FORMAT
DEFAULT
Summary of Contents for C60 UR series
Page 2: ......
Page 4: ......
Page 11: ...GE Multilin C60 Breaker Protection System xi TABLE OF CONTENTS INDEX...
Page 12: ...xii C60 Breaker Protection System GE Multilin TABLE OF CONTENTS...
Page 32: ...1 20 C60 Breaker Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1...
Page 50: ...2 18 C60 Breaker Protection System GE Multilin 2 2 SPECIFICATIONS 2 PRODUCT DESCRIPTION 2...
Page 128: ...4 30 C60 Breaker Protection System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4...
Page 394: ...9 4 C60 Breaker Protection System GE Multilin 9 1 FAULT LOCATOR 9 THEORY OF OPERATION 9...
Page 516: ...D 10 C60 Breaker Protection System GE Multilin D 1 OVERVIEW APPENDIXD D...
Page 528: ...E 12 C60 Breaker Protection System GE Multilin E 2 DNP POINT LISTS APPENDIXE E...