5-32
C60 Breaker Protection System
GE Multilin
5.2 PRODUCT SETUP
5 SETTINGS
5
The breaker configuration settings are shown below. Changes to these values will not take effect until the UR is restarted:
PATH: SETTINGS
Ö
PRODUCT SETUP
ÖØ
COMMUNICATIONS
ÖØ
IEC 61850 PROTOCOL
ÖØ
XCBR CONFIGURATION
The
CLEAR XCBR1 OpCnt
setting represents the breaker operating counter. As breakers operate by opening and closing, the
XCBR operating counter status attribute (OpCnt) increments with every operation. Frequent breaker operation may result
in very large OpCnt values over time. This setting allows the OpCnt to be reset to “0” for XCBR1.
The disconnect switch configuration settings are shown below. Changes to these values will not take effect until the UR is
restarted:
PATH: SETTINGS
Ö
PRODUCT SETUP
ÖØ
COMMUNICATIONS
ÖØ
IEC 61850 PROTOCOL
ÖØ
XSWI CONFIGURATION
The
CLEAR XSWI1 OpCnt
setting represents the disconnect switch operating counter. As disconnect switches operate by
opening and closing, the XSWI operating counter status attribute (OpCnt) increments with every operation. Frequent switch
operation may result in very large OpCnt values over time. This setting allows the OpCnt to be reset to “0” for XSWI1.
Since GSSE/GOOSE messages are multicast Ethernet by specification, they will not usually be forwarded by net-
work routers. However, GOOSE messages may be fowarded by routers if the router has been configured for VLAN
functionality.
XCBR
CONFIGURATION
XCBR1 ST.LOC OPERAND
Off
Range: FlexLogic™ operand
MESSAGE
XCBR2 ST.LOC OPERAND
Off
Range: FlexLogic™ operand
↓
MESSAGE
XCBR6 ST.LOC OPERAND
Off
Range: FlexLogic™ operand
MESSAGE
CLEAR XCBR1 OpCnt:
No
Range: No, Yes
MESSAGE
CLEAR XCBR2 OpCnt:
No
Range: No, Yes
↓
MESSAGE
CLEAR XCBR6 OpCnt:
No
Range: No, Yes
XSWI
CONFIGURATION
XSWI1 ST.LOC OPERAND
Off
Range: FlexLogic™ operand
MESSAGE
XSWI2 ST.LOC OPERAND
Off
Range: FlexLogic™ operand
↓
MESSAGE
XSWI24 ST.LOC OPERAND
Off
Range: FlexLogic™ operand
MESSAGE
CLEAR XSWI1 OpCnt:
No
Range: No, Yes
MESSAGE
CLEAR XSWI2 OpCnt:
No
Range: No, Yes
↓
MESSAGE
CLEAR XSWI24 OpCnt:
No
Range: No, Yes
NOTE
Summary of Contents for C60
Page 2: ......
Page 4: ......
Page 11: ...GE Multilin C60 Breaker Protection System xi TABLE OF CONTENTS INDEX ...
Page 12: ...xii C60 Breaker Protection System GE Multilin TABLE OF CONTENTS ...
Page 32: ...1 20 C60 Breaker Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Page 50: ...2 18 C60 Breaker Protection System GE Multilin 2 2 SPECIFICATIONS 2 PRODUCT DESCRIPTION 2 ...
Page 128: ...4 30 C60 Breaker Protection System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Page 394: ...9 4 C60 Breaker Protection System GE Multilin 9 1 FAULT LOCATOR 9 THEORY OF OPERATION 9 ...
Page 516: ...D 10 C60 Breaker Protection System GE Multilin D 1 OVERVIEW APPENDIXD D ...
Page 528: ...E 12 C60 Breaker Protection System GE Multilin E 2 DNP POINT LISTS APPENDIXE E ...