6-6
C60 Breaker Protection System
GE Multilin
6.2 STATUS
6 ACTUAL VALUES
6
b) STATISTICS
PATH: ACTUAL VALUES
Ö
STATUS
ÖØ
REMOTE DEVICES STATISTICS
Ö
REMOTE DEVICE 1(16)
Statistical data (two types) for up to 16 programmed remote devices is shown here.
The
StNum
number is obtained from the indicated remote device and is incremented whenever a change of state of at
least one DNA or UserSt bit occurs. The
SqNum
number is obtained from the indicated remote device and is incremented
whenever a GSSE message is sent. This number will rollover to zero when a count of 4 294 967 295 is incremented.
6.2.10 DIGITAL COUNTERS
PATH: ACTUAL VALUES
Ö
STATUS
ÖØ
DIGITAL COUNTERS
Ö
DIGITAL COUNTERS Counter 1(8)
The present status of the eight digital counters is shown here. The status of each counter, with the user-defined counter
name, includes the accumulated and frozen counts (the count units label will also appear). Also included, is the date and
time stamp for the frozen count. The
COUNTER 1 MICROS
value refers to the microsecond portion of the time stamp.
6.2.11 SELECTOR SWITCHES
PATH: ACTUAL VALUES
Ö
STATUS
ÖØ
SELECTOR SWITCHES
The display shows both the current position and the full range. The current position only (an integer from 0 through 7) is the
actual value.
6.2.12 FLEX STATES
PATH: ACTUAL VALUES
Ö
STATUS
ÖØ
FLEX STATES
REMOTE DEVICE 1
REMOTE DEVICE 1
StNum: 0
MESSAGE
REMOTE DEVICE 1
SqNum: 0
DIGITAL COUNTERS
Counter 1
Counter 1
ACCUM:
0
MESSAGE
Counter 1
FROZEN:
0
MESSAGE
Counter 1
FROZEN:
YYYY/MM/DD HH:MM:SS
MESSAGE
Counter 1
MICROS:
0
SELECTOR SWITCHES
SELECTOR SWITCH 1
POSITION: 0/7
Range: Current Position / 7
MESSAGE
SELECTOR SWITCH 2
POSITION: 0/7
Range: Current Position / 7
FLEX STATES
PARAM 1:
Off
Off
Range: Off, On
MESSAGE
PARAM 2:
Off
Off
Range: Off, On
↓
MESSAGE
PARAM 256: Off
Off
Range: Off, On
Summary of Contents for C60
Page 2: ......
Page 4: ......
Page 11: ...GE Multilin C60 Breaker Protection System xi TABLE OF CONTENTS INDEX ...
Page 12: ...xii C60 Breaker Protection System GE Multilin TABLE OF CONTENTS ...
Page 32: ...1 20 C60 Breaker Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Page 50: ...2 18 C60 Breaker Protection System GE Multilin 2 2 SPECIFICATIONS 2 PRODUCT DESCRIPTION 2 ...
Page 128: ...4 30 C60 Breaker Protection System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Page 394: ...9 4 C60 Breaker Protection System GE Multilin 9 1 FAULT LOCATOR 9 THEORY OF OPERATION 9 ...
Page 516: ...D 10 C60 Breaker Protection System GE Multilin D 1 OVERVIEW APPENDIXD D ...
Page 528: ...E 12 C60 Breaker Protection System GE Multilin E 2 DNP POINT LISTS APPENDIXE E ...