GE Multilin
C60 Breaker Protection System
B-43
APPENDIX B
B.4 MEMORY MAPPING
B
B013
IEC 61850 GSSE ID
---
---
---
F209
“GSSEOut”
B03F
IEC 61850 GOOSE Function (GoEna)
0 to 1
---
1
F102
0 (Disabled)
B040
IEC 61850 GSSE Destination MAC Address
---
---
---
F072
0
B043
IEC 61850 Standard GOOSE ID
---
---
---
F209
“GOOSEOut”
B064
IEC 61850 Standard GOOSE Destination MAC Address
---
---
---
F072
0
B067
IEC 61850 GOOSE VLAN Transmit Priority
0 to 7
---
1
F001
4
B068
IEC 61850 GOOSE VLAN ID
0 to 4095
---
1
F001
0
B069
IEC 61850 GOOSE ETYPE APPID
0 to 16383
---
1
F001
0
B06A
Reserved (2 items)
0 to 1
---
1
F001
0
IEC 61850 Server Configuration (Read/Write Settings/Commands)
B06C
TCP Port Number for the IEC 61850 / MMS Protocol
1 to 65535
---
1
F001
102
B06D
IEC 61850 Logical Device Name
---
---
---
F213
“IECName”
B07D
IEC 61850 Logical Device Instance
---
---
---
F213
“LDInst”
B08D
IEC 61850 LPHD Location
---
---
---
F204
“Location”
B0B5
Include non-IEC 61850 Data
0 to 1
---
1
F102
0 (Disabled)
B06B
IEC 61850 Server Data Scanning Function
0 to 1
---
1
F102
0 (Disabled)
B0B7
Reserved (15 items)
IEC 61850 MMXU Deadbands (Read/Write Setting) (6 modules)
B0C0
IEC 61850 MMXU TotW Deadband 1
0.001 to 100
%
0.001
F003
10000
B0C2
IEC 61850 MMXU TotVAr Deadband 1
0.001 to 100
%
0.001
F003
10000
B0C4
IEC 61850 MMXU TotVA Deadband 1
0.001 to 100
%
0.001
F003
10000
B0C6
IEC 61850 MMXU TotPF Deadband 1
0.001 to 100
%
0.001
F003
10000
B0C8
IEC 61850 MMXU Hz Deadband 1
0.001 to 100
%
0.001
F003
10000
B0CA
IEC 61850 MMXU PPV.phsAB Deadband 1
0.001 to 100
%
0.001
F003
10000
B0CC
IEC 61850 MMXU PPV.phsBC Deadband 1
0.001 to 100
%
0.001
F003
10000
B0CE
IEC 61850 MMXU PPV.phsCA Deadband 1
0.001 to 100
%
0.001
F003
10000
B0D0
IEC 61850 MMXU PhV.phsADeadband 1
0.001 to 100
%
0.001
F003
10000
B0D2
IEC 61850 MMXU PhV.phsB Deadband 1
0.001 to 100
%
0.001
F003
10000
B0D4
IEC 61850 MMXU PhV.phsC Deadband 1
0.001 to 100
%
0.001
F003
10000
B0D6
IEC 61850 MMXU A.phsA Deadband 1
0.001 to 100
%
0.001
F003
10000
B0D8
IEC 61850 MMXU A.phsB Deadband 1
0.001 to 100
%
0.001
F003
10000
B0DA
IEC 61850 MMXU A.phsC Deadband 1
0.001 to 100
%
0.001
F003
10000
B0DC
IEC 61850 MMXU A.neut Deadband 1
0.001 to 100
%
0.001
F003
10000
B0DE
IEC 61850 MMXU W.phsA Deadband 1
0.001 to 100
%
0.001
F003
10000
B0E0
IEC 61850 MMXU W.phsB Deadband 1
0.001 to 100
%
0.001
F003
10000
B0E2
IEC 61850 MMXU W.phsC Deadband 1
0.001 to 100
%
0.001
F003
10000
B0E4
IEC 61850 MMXU VAr.phsA Deadband 1
0.001 to 100
%
0.001
F003
10000
B0E6
IEC 61850 MMXU VAr.phsB Deadband 1
0.001 to 100
%
0.001
F003
10000
B0E8
IEC 61850 MMXU VAr.phsC Deadband 1
0.001 to 100
%
0.001
F003
10000
B0EA
IEC 61850 MMXU VA.phsA Deadband 1
0.001 to 100
%
0.001
F003
10000
B0EC
IEC 61850 MMXU VA.phsB Deadband 1
0.001 to 100
%
0.001
F003
10000
B0EE
IEC 61850 MMXU VA.phsC Deadband 1
0.001 to 100
%
0.001
F003
10000
B0F0
IEC 61850 MMXU PF.phsA Deadband 1
0.001 to 100
%
0.001
F003
10000
B0F2
IEC 61850 MMXU PF.phsB Deadband 1
0.001 to 100
%
0.001
F003
10000
B0F4
IEC 61850 MMXU PF.phsC Deadband 1
0.001 to 100
%
0.001
F003
10000
B0F6
...Repeated for Deadband 2
B12C
...Repeated for Deadband 3
B162
...Repeated for Deadband 4
B198
...Repeated for Deadband 5
B1CE
...Repeated for Deadband 6
IEC 61850 Report Settings (Read/Write Setting) (14 modules)
B280
IEC 61850 Report Control 1 RptID
---
---
---
F209
B2A1
IEC 61850 Report Control 1 OptFlds
0 to 65535
---
1
F001
0
B2A2
IEC 61850 Report Control 1 BufTm
0 to 4294967295
---
1
F003
0
Table B–9: MODBUS MEMORY MAP (Sheet 36 of 50)
ADDR
REGISTER NAME
RANGE
UNITS
STEP
FORMAT
DEFAULT
Summary of Contents for C60
Page 2: ......
Page 4: ......
Page 11: ...GE Multilin C60 Breaker Protection System xi TABLE OF CONTENTS INDEX ...
Page 12: ...xii C60 Breaker Protection System GE Multilin TABLE OF CONTENTS ...
Page 32: ...1 20 C60 Breaker Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Page 50: ...2 18 C60 Breaker Protection System GE Multilin 2 2 SPECIFICATIONS 2 PRODUCT DESCRIPTION 2 ...
Page 128: ...4 30 C60 Breaker Protection System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Page 394: ...9 4 C60 Breaker Protection System GE Multilin 9 1 FAULT LOCATOR 9 THEORY OF OPERATION 9 ...
Page 516: ...D 10 C60 Breaker Protection System GE Multilin D 1 OVERVIEW APPENDIXD D ...
Page 528: ...E 12 C60 Breaker Protection System GE Multilin E 2 DNP POINT LISTS APPENDIXE E ...