APPENDIX B
B.4 MEMORY MAPPING
B
F082
ENUMERATION: AUTORECLOSE SINGLE-PHASE /
THREE-PHASE BREAKER SEQUENCE
0 = 1, 1 = 2, 2 = 1 & 2, 3 = 1 – 2, 4 = 2 – 1
F083
ENUMERATION: SELECTOR MODES
0 = Time-Out, 1 = Acknowledge
F084
ENUMERATION: SELECTOR POWER UP
0 = Restore, 1 = Synchronize, 2 = Sync/Restore
F086
ENUMERATION: DIGITAL INPUT DEFAULT STATE
0 = Off, 1 = On, 2= Latest/Off, 3 = Latest/On
F090
ENUMERATION: LATCHING OUTPUT TYPE
0 = Operate-dominant, 1 = Reset-dominant
F100
ENUMERATION: VT CONNECTION TYPE
0 = Wye; 1 = Delta
F101
ENUMERATION: MESSAGE DISPLAY INTENSITY
0 = 25%, 1 = 50%, 2 = 75%, 3 = 100%
F102
ENUMERATION: DISABLED/ENABLED
0 = Disabled; 1 = Enabled
F103
ENUMERATION: CURVE SHAPES
F104
ENUMERATION: RESET TYPE
0 = Instantaneous, 1 = Timed, 2 = Linear
F105
ENUMERATION: LOGIC INPUT
0 = Disabled, 1 = Input 1, 2 = Input 2
F106
ENUMERATION: PHASE ROTATION
0 = ABC, 1 = ACB
F108
ENUMERATION: OFF/ON
0 = Off, 1 = On
F109
ENUMERATION: CONTACT OUTPUT OPERATION
0 = Self-reset, 1 = Latched, 2 = Disabled
F110
ENUMERATION: CONTACT OUTPUT LED CONTROL
0 = Trip, 1 = Alarm, 2 = None
F111
ENUMERATION: UNDERVOLTAGE CURVE SHAPES
0 = Definite Time, 1 = Inverse Time
F112
ENUMERATION: RS485 BAUD RATES
F113
ENUMERATION: PARITY
0 = None, 1 = Odd, 2 = Even
F114
ENUMERATION: IRIG-B SIGNAL TYPE
0 = None, 1 = DC Shift, 2 = Amplitude Modulated
F115
ENUMERATION: BREAKER STATUS
0 = Auxiliary A, 1 = Auxiliary B
bitmask
curve shape
bitmask
curve shape
0
IEEE Mod Inv
9
IAC Inverse
1
IEEE Very Inv
10
IAC Short Inv
2
IEEE Ext Inv
11
I2t
3
IEC Curve A
12
Definite Time
4
IEC Curve B
13
FlexCurve™ A
5
IEC Curve C
14
FlexCurve™ B
6
IEC Short Inv
15
FlexCurve™ C
7
IAC Ext Inv
16
FlexCurve™ D
8
IAC Very Inv
bitmask
value
bitmask
value
bitmask
value
0
300
4
9600
8
115200
1
1200
5
19200
9
14400
2
2400
6
38400
10
28800
3
4800
7
57600
11
33600
Summary of Contents for C60
Page 2: ......
Page 4: ......
Page 11: ...GE Multilin C60 Breaker Protection System xi TABLE OF CONTENTS INDEX ...
Page 12: ...xii C60 Breaker Protection System GE Multilin TABLE OF CONTENTS ...
Page 32: ...1 20 C60 Breaker Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Page 50: ...2 18 C60 Breaker Protection System GE Multilin 2 2 SPECIFICATIONS 2 PRODUCT DESCRIPTION 2 ...
Page 128: ...4 30 C60 Breaker Protection System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Page 394: ...9 4 C60 Breaker Protection System GE Multilin 9 1 FAULT LOCATOR 9 THEORY OF OPERATION 9 ...
Page 516: ...D 10 C60 Breaker Protection System GE Multilin D 1 OVERVIEW APPENDIXD D ...
Page 528: ...E 12 C60 Breaker Protection System GE Multilin E 2 DNP POINT LISTS APPENDIXE E ...