GE Multilin
C60 Breaker Protection System
3-23
3 HARDWARE
3.2 WIRING
3
3.2.8 RS232 FACEPLATE PORT
A 9-pin RS232C serial port is located on the C60 faceplate for programming with a personal computer. All that is required to
use this interface is a personal computer running the EnerVista UR Setup software provided with the relay. Cabling for the
RS232 port is shown in the following figure for both 9-pin and 25-pin connectors.
The baud rate for this port is fixed at
19200 bps
.
Figure 3–23: RS232 FACEPLATE PORT CONNECTION
3.2.9 CPU COMMUNICATION PORTS
a) OPTIONS
In addition to the faceplate RS232 port, the C60 provides two additional communication ports or a managed six-port Ether-
net switch, depending on the installed CPU module.
The CPU modules do not require a surge ground connection.
Table 3–3: CPU MODULE COMMUNICATIONS
CPU TYPE
COM1
COM2
9E
RS485
RS485
9G
10Base-F and 10Base-T
RS485
9H
Redundant 10Base-F
RS485
9J
100Base-FX
RS485
9K
Redundant 100Base-FX
RS485
9L
100Base-FX
RS485
9M
Redundant 100Base-FX
RS485
9N
10/100Base-T
RS485
9P
100Base-FX
RS485
9R
Redundant 100Base-FX
RS485
9S
Ethernet switch module with two 10/100Base-T and four 100Base-FX ports
RS485
NOTE
NOTE
Summary of Contents for C60
Page 2: ......
Page 4: ......
Page 11: ...GE Multilin C60 Breaker Protection System xi TABLE OF CONTENTS INDEX ...
Page 12: ...xii C60 Breaker Protection System GE Multilin TABLE OF CONTENTS ...
Page 32: ...1 20 C60 Breaker Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Page 50: ...2 18 C60 Breaker Protection System GE Multilin 2 2 SPECIFICATIONS 2 PRODUCT DESCRIPTION 2 ...
Page 128: ...4 30 C60 Breaker Protection System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Page 394: ...9 4 C60 Breaker Protection System GE Multilin 9 1 FAULT LOCATOR 9 THEORY OF OPERATION 9 ...
Page 516: ...D 10 C60 Breaker Protection System GE Multilin D 1 OVERVIEW APPENDIXD D ...
Page 528: ...E 12 C60 Breaker Protection System GE Multilin E 2 DNP POINT LISTS APPENDIXE E ...