GE Multilin
C60 Breaker Protection System
4-27
4 HUMAN INTERFACES
4.3 FACEPLATE INTERFACE
4
There are several places where text messages may be programmed to allow the relay to be customized for specific appli-
cations. One example is the Message Scratchpad. Use the following procedure to enter alphanumeric text messages.
For example: to enter the text, “Breaker #1”.
1.
Press the decimal to enter text edit mode.
2.
Press the VALUE keys until the character 'B' appears; press the decimal key to advance the cursor to the next position.
3.
Repeat step 2 for the remaining characters: r,e,a,k,e,r, ,#,1.
4.
Press ENTER to store the text.
5.
If you have any problem, press HELP to view context sensitive help. Flash messages will sequentially appear for sev-
eral seconds each. For the case of a text setting message, pressing HELP displays how to edit and store new values.
d) ACTIVATING THE RELAY
To change the
RELAY SETTINGS
: "Not Programmed" mode to "Programmed", proceed as follows:
1.
Press the MENU key until the
SETTINGS
header flashes momentarily and the
PRODUCT SETUP
message appears on the
display.
2.
Press the MESSAGE RIGHT key until the
PASSWORD SECURITY
message appears on the display.
3.
Press the MESSAGE DOWN key until the
INSTALLATION
message appears on the display.
4.
Press the MESSAGE RIGHT key until the
RELAY SETTINGS:
Not Programmed
message is displayed.
5.
After the
RELAY SETTINGS:
Not Programmed
message appears on the display, press the VALUE keys change the
selection to "Programmed".
6.
Press the ENTER key.
7.
When the "NEW SETTING HAS BEEN STORED" message appears, the relay will be in "Programmed" state and the
In Service LED will turn on.
e) ENTERING INITIAL PASSWORDS
The C60 supports password entry from a local or remote connection.
RELAY SETTINGS:
Not Programmed
When the relay is powered up, the Trouble LED will be on, the In Service LED off, and
this message displayed, indicating the relay is in the "Not Programmed" state and is safe-
guarding (output relays blocked) against the installation of a relay whose settings have
not been entered. This message remains until the relay is explicitly put in the "Pro-
grammed" state.
SETTINGS
Ø
SETTINGS
PRODUCT SETUP
PASSWORD
SECURITY
DISPLAY
PROPERTIES
↓
INSTALLATION
RELAY SETTINGS:
Not Programmed
RELAY SETTINGS:
Not Programmed
RELAY SETTINGS:
Programmed
NEW SETTING
HAS BEEN STORED
Summary of Contents for C60
Page 2: ......
Page 4: ......
Page 11: ...GE Multilin C60 Breaker Protection System xi TABLE OF CONTENTS INDEX ...
Page 12: ...xii C60 Breaker Protection System GE Multilin TABLE OF CONTENTS ...
Page 32: ...1 20 C60 Breaker Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Page 50: ...2 18 C60 Breaker Protection System GE Multilin 2 2 SPECIFICATIONS 2 PRODUCT DESCRIPTION 2 ...
Page 128: ...4 30 C60 Breaker Protection System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Page 394: ...9 4 C60 Breaker Protection System GE Multilin 9 1 FAULT LOCATOR 9 THEORY OF OPERATION 9 ...
Page 516: ...D 10 C60 Breaker Protection System GE Multilin D 1 OVERVIEW APPENDIXD D ...
Page 528: ...E 12 C60 Breaker Protection System GE Multilin E 2 DNP POINT LISTS APPENDIXE E ...