5-136
C60 Breaker Protection System
GE Multilin
5.6 GROUPED ELEMENTS
5 SETTINGS
5
Figure 5–61: INVERSE TIME UNDERVOLTAGE CURVES
At 0% of pickup, the operating time equals the
UNDERVOLTAGE DELAY
setting.
b) PHASE UNDERVOLTAGE
(ANSI 27P)
PATH: SETTINGS
ÖØ
GROUPED ELEMENTS
Ö
SETTING GROUP 1(6)
ÖØ
VOLTAGE ELEMENTS
Ö
PHASE UNDERVOLTAGE1(3)
This element may be used to give a desired time-delay operating characteristic versus the applied fundamental voltage
(phase-to-ground or phase-to-phase for wye VT connection, or phase-to-phase for delta VT connection) or as a definite
time element. The element resets instantaneously if the applied voltage exceeds the dropout voltage. The delay setting
selects the minimum operating time of the phase undervoltage. The minimum voltage setting selects the operating voltage
below which the element is blocked (a setting of “0” will allow a dead source to be considered a fault condition).
PHASE
UNDERVOLTAGE1
PHASE UV1
FUNCTION: Disabled
Range: Disabled, Enabled
MESSAGE
PHASE UV1 SIGNAL
SOURCE: SRC 1
Range: SRC 1, SRC 2, SRC 3, SRC 4
MESSAGE
PHASE UV1 MODE:
Phase to Ground
Range: Phase to Ground, Phase to Phase
MESSAGE
PHASE UV1
PICKUP: 1.000 pu
Range: 0.000 to 3.000 pu in steps of 0.001
MESSAGE
PHASE UV1
CURVE: Definite Time
Range: Definite Time, Inverse Time
MESSAGE
PHASE UV1
DELAY: 1.00
s
Range: 0.00 to 600.00 s in steps of 0.01
MESSAGE
PHASE UV1 MINIMUM
VOLTAGE: 0.100 pu
Range: 0.000 to 3.000 pu in steps of 0.001
MESSAGE
PHASE UV1 BLOCK:
Off
Range: FlexLogic™ operand
MESSAGE
PHASE UV1
TARGET: Self-reset
Range: Self-reset, Latched, Disabled
MESSAGE
PHASE UV1
EVENTS: Disabled
Range: Disabled, Enabled
842788A1.CDR
% of voltage pickup
Time
(seconds)
NOTE
Summary of Contents for C60
Page 2: ......
Page 4: ......
Page 11: ...GE Multilin C60 Breaker Protection System xi TABLE OF CONTENTS INDEX ...
Page 12: ...xii C60 Breaker Protection System GE Multilin TABLE OF CONTENTS ...
Page 32: ...1 20 C60 Breaker Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Page 50: ...2 18 C60 Breaker Protection System GE Multilin 2 2 SPECIFICATIONS 2 PRODUCT DESCRIPTION 2 ...
Page 128: ...4 30 C60 Breaker Protection System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Page 394: ...9 4 C60 Breaker Protection System GE Multilin 9 1 FAULT LOCATOR 9 THEORY OF OPERATION 9 ...
Page 516: ...D 10 C60 Breaker Protection System GE Multilin D 1 OVERVIEW APPENDIXD D ...
Page 528: ...E 12 C60 Breaker Protection System GE Multilin E 2 DNP POINT LISTS APPENDIXE E ...