5-138
C60 Breaker Protection System
GE Multilin
5.6 GROUPED ELEMENTS
5 SETTINGS
5
VT errors and normal voltage unbalance must be considered when setting this element. This function requires the VTs to
be wye-connected.
Figure 5–63: NEUTRAL OVERVOLTAGE1 SCHEME LOGIC
d) AUXILIARY UNDERVOLTAGE
(ANSI 27X)
PATH: SETTINGS
ÖØ
GROUPED ELEMENTS
Ö
SETTING GROUP 1(6)
ÖØ
VOLTAGE ELEMENTS
ÖØ
AUXILIARY UV1(2)
The C60 contains one auxiliary undervoltage element for each VT bank. This element is intended for monitoring undervolt-
age conditions of the auxiliary voltage. The
AUX UV1 PICKUP
selects the voltage level at which the time undervoltage ele-
ment starts timing. The nominal secondary voltage of the auxiliary voltage channel entered under
SETTINGS
ÖØ
SYSTEM
SETUP
Ö
AC INPUTS
ÖØ
VOLTAGE BANK X5
ÖØ
AUXILIARY VT X5 SECONDARY
is the per-unit base used when setting the
pickup level.
The
AUX UV1 DELAY
setting selects the minimum operating time of the auxiliary undervoltage element. Both
AUX UV1 PICKUP
and
AUX UV1 DELAY
settings establish the operating curve of the undervoltage element. The auxiliary undervoltage element
can be programmed to use either definite time delay or inverse time delay characteristics. The operating characteristics
and equations for both definite and inverse time delay are as for the phase undervoltage element.
AUXILIARY UV1
AUX UV1
FUNCTION: Disabled
Range: Disabled, Enabled
MESSAGE
AUX UV1 SIGNAL
SOURCE: SRC 1
Range: SRC 1, SRC 2, SRC 3, SRC 4
MESSAGE
AUX UV1 PICKUP:
0.700 pu
Range: 0.000 to 3.000 pu in steps of 0.001
MESSAGE
AUX UV1 CURVE:
Definite Time
Range: Definite Time, Inverse Time
MESSAGE
AUX UV1 DELAY:
1.00 s
Range: 0.00 to 600.00 s in steps of 0.01
MESSAGE
AUX UV1 MINIMUM:
VOLTAGE: 0.100 pu
Range: 0.000 to 3.000 pu in steps of 0.001
MESSAGE
AUX UV1 BLOCK:
Off
Range: FlexLogic™ operand
MESSAGE
AUX UV1 TARGET:
Self-reset
Range: Self-reset, Latched, Disabled
MESSAGE
AUX UV1 EVENTS:
Disabled
Range: Disabled, Enabled
Summary of Contents for C60
Page 2: ......
Page 4: ......
Page 11: ...GE Multilin C60 Breaker Protection System xi TABLE OF CONTENTS INDEX ...
Page 12: ...xii C60 Breaker Protection System GE Multilin TABLE OF CONTENTS ...
Page 32: ...1 20 C60 Breaker Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Page 50: ...2 18 C60 Breaker Protection System GE Multilin 2 2 SPECIFICATIONS 2 PRODUCT DESCRIPTION 2 ...
Page 128: ...4 30 C60 Breaker Protection System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Page 394: ...9 4 C60 Breaker Protection System GE Multilin 9 1 FAULT LOCATOR 9 THEORY OF OPERATION 9 ...
Page 516: ...D 10 C60 Breaker Protection System GE Multilin D 1 OVERVIEW APPENDIXD D ...
Page 528: ...E 12 C60 Breaker Protection System GE Multilin E 2 DNP POINT LISTS APPENDIXE E ...