GE Multilin
C60 Breaker Protection System
3-47
3 HARDWARE
3.4 MANAGED ETHERNET SWITCH MODULES
3
3.4.6 ETHERNET SWITCH SELF-TEST ERRORS
The following table provides details about Ethernet module self-test errors.
Be sure to enable the
ETHERNET SWITCH FAIL
setting in the
PRODUCT SETUP
ÖØ
USER-PROGRAMMABLE SELF-TESTS
menu
and the relevant
PORT 1 EVENTS
through
PORT 6 EVENTS
settings under the
PRODUCT SETUP
ÖØ
COMMUNICATIONS
ÖØ
ETH-
ERNET SWITCH
menu.
Table 3–7: ETHERNET SWITCH SELF-TEST ERRORS
ACTIVATION SETTING (SET
AS ENABLED)
EVENT NAME
EVENT CAUSE
POSSIBLE CAUSES
ETHERNET SWITCH FAIL
ETHERNET MODULE
OFFLINE
No response has been
received from the Ethernet
module after five successive
polling attempts.
• Loss of switch power.
• IP/gateway/subnet.
• Incompatibility between the CPU and
the switch module.
• UR port (port 7) configured incorrectly
or blocked
• Switch IP address assigned to another
device in the same network.
PORT 1 EVENTS to PORT 6
EVENTS
ETHERNET PORT 1
OFFLINE to ETHERNET
PORT 6 OFFLINE
An active Ethernet port has
returned a FAILED status.
• Ethernet connection broken.
• An inactive port’s events have been
enabled.
No setting required; the C60
will read the state of a general
purpose input/output port on
the main CPU upon power-up
and create the error if there is a
conflict between the input/
output state and the order
code.
EQUIPMENT
MISMATCH: Card XXX
Missing
The C60 has not detected the
presence of the Ethernet
switch via the bus board.
The C60 failed to see the switch module
on power-up, because switch won’t
power up or is still powering up. To clear
the fault, cycle power to the C60.
Summary of Contents for C60
Page 2: ......
Page 4: ......
Page 11: ...GE Multilin C60 Breaker Protection System xi TABLE OF CONTENTS INDEX ...
Page 12: ...xii C60 Breaker Protection System GE Multilin TABLE OF CONTENTS ...
Page 32: ...1 20 C60 Breaker Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Page 50: ...2 18 C60 Breaker Protection System GE Multilin 2 2 SPECIFICATIONS 2 PRODUCT DESCRIPTION 2 ...
Page 128: ...4 30 C60 Breaker Protection System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Page 394: ...9 4 C60 Breaker Protection System GE Multilin 9 1 FAULT LOCATOR 9 THEORY OF OPERATION 9 ...
Page 516: ...D 10 C60 Breaker Protection System GE Multilin D 1 OVERVIEW APPENDIXD D ...
Page 528: ...E 12 C60 Breaker Protection System GE Multilin E 2 DNP POINT LISTS APPENDIXE E ...