9. ACCEPTANCE TESTS
9-4
DTP-B Digital Transformer Protection
GEK-106243E
9.8 COMMUNICATION PORTS CHECKING
This test is performed to check that the 3 communications ports operate correctly.
To do this, it is necessary to connect the relay to a PC using the connectors shown in figure 3.
Set the following communications parameters for the computer and the relay:
Relay number = 1
Network baud rate = 9600
Local baud rate = 9600
Remote stop bits = 1
Local stop bits = 1
Using the GE-LOCAL communications software, perform the connection and check that the relay communicates
by both ports. Repeat the test for different baud rates.
9.9 KEYPAD, DISPLAY, AND LEDS CHECKING.
Press the Target Reset button and verify that all the LEDs light up.
Press the appropriate keys and verify that the following messages are displayed:
KEY
MESSAGE
< SET >
VIEW PROTECTION SETTINGS
< CLR >
DTP GENERAL ELECTRIC
< INF >
STATUS
< ENT >
MODEL
<
↑
>
DATABASE
<
↓
>
MODEL
< CLR >
STATUS
< CLR >
DTP GENERAL ELECTRIC
< ACT >
SET DATE/TIME
< CLR >
DTP GENERAL ELECTRIC
<7169>
NET BAUD RATE
<
↑
>
NET STOP BITS
Now, dial all the numbers one by one, deleting them with the CLR key, and check that the pressed numbers are
displayed.
Summary of Contents for DTP-B
Page 23: ...3 OPERATING PRINCIPLES 3 6 DTP B Digital Transformer Protection GEK 106243E ...
Page 53: ...10 INSTALLATION AND MAINTENANCE 10 2 DTP B Digital Transformer Protection GEK 106243E ...
Page 68: ...12 FIGURES GEK 106243E DTP Digital Transformer Protection 12 3 Figure 3 RS 232 Connection ...
Page 69: ...12 FIGURES 12 4 DTP B Digital Transformer Protection GEK 106243E Figure 4 Dimensions Diagram ...
Page 70: ...12 FIGURES GEK 106243E DTP Digital Transformer Protection 12 5 Figure 5 Front View ...