11. KEYBOARD AND DISPLAY
11-4
DTP-B Digital Transformer Protection
GEK-106243E
11.2 SETTINGS GROUP
This group allows the visualization and modification of the DTP settings. It is accessed by pressing the SET key
when the DTP is in the initial screen. When the SET key is pressed the following message appears on the screen:
When the UP/DOWN arrows are pressed the message changes to:
The menu tree for the DTP settings is shown in the following table. Note that to go down a level in the tree you
have to press the ENT key and that to go up you have to press the CLR key.
Level 1
Level 2
Level 3
Presentation
Valid Range
VIEW
PROTECTION
SETTINGS
GENERAL
SETTINGS
RELAY STATUS
It sets the relay in / out of service
In / Out of
service
MODIFY
PROTECTION
SETTINGS
IDENTIFICAT.
20 character alphanumeric string
FREQUENCY
Rated
frequency of the relay
50/60 Hz
1
st
WDG CT RATIO
1
st
winding CT ratio
1 - 4000 in steps
of 1
2
nd
WDG CT RATIO
2
nd
winding CT ratio
1 - 4000 in steps
of 1
3
rd
WDG CT RATIO
3
rd
winding CT ratio
1 - 4000 in steps
of 1
4
th
WDG CT RATIO
4
th
winding CT ratio
1 - 4000 in steps
of 1
COMPENSATION
Type of compensation (External or
internal)
ACTIVE
TABLE
SET
ACTIVE TABLE
It allows changing the active table
1-3
PROTECTION
SETTINGS
1
st
WINDING TAP
Change from winding current to
CT current
.5 to 20 in steps
of 0.01 x In
2
nd
WINDING TAP
Change from winding current to
CT current
.5 to 20 in steps
of 0.01 x In
3
rd
WINDING TAP
Change from winding current to
CT current
.5 to 20 in steps
of 0.01 x In
4
th
WINDING TAP
Change from winding current to
CT current
.5 to 20 in steps
of 0.01 x In
VIEW PROTECTION
SETTINGS
MODIFY PROTECTION
SETTINGS
Summary of Contents for DTP-B
Page 23: ...3 OPERATING PRINCIPLES 3 6 DTP B Digital Transformer Protection GEK 106243E ...
Page 53: ...10 INSTALLATION AND MAINTENANCE 10 2 DTP B Digital Transformer Protection GEK 106243E ...
Page 68: ...12 FIGURES GEK 106243E DTP Digital Transformer Protection 12 3 Figure 3 RS 232 Connection ...
Page 69: ...12 FIGURES 12 4 DTP B Digital Transformer Protection GEK 106243E Figure 4 Dimensions Diagram ...
Page 70: ...12 FIGURES GEK 106243E DTP Digital Transformer Protection 12 5 Figure 5 Front View ...