1. GENERAL DESCRIPTION
GEK-106243E
DTP Digital Transformer Protection
1-1
1. GENERAL DESCRIPTION
During the last years, new technologies have achieved an important improvement in the concept of function
integration between the different components of electrical systems. There are several reasons for that integration:
•
Reduce the investment in new equipment.
•
Optimize the use of the existing installations.
•
Improve the energy management system.
This function integration not only includes the high and low voltage switchgear protection and control devices,
protection of different elements, signalling and alarms of a substation, but also the monitoring of all elements, the
analysis of the great amount of available information (events, alarms, oscillography, load and demand profiles),
and certainly innovative functions, such as substation maintenance, adaptive protections, etc.
The DTP is a digital relay that provides differential (87) and backup instantaneous (87B) three phase protection
functions for power transformers. Different models of the DTP are available for protecting and monitoring
transformers with two, three, or four windings.
This equipment incorporates the following functions:
a) Protection
•
Totally digital three phase differential protection (87) with percentage restraint and harmonic restraint (second
and fifth harmonic).
•
Programmable backup differential instantaneous protection (87B).
•
Additional dynamic harmonic restraint (innovative function compared to static harmonic restraint)
•
Digital filtering of the zero-sequence component of the applied current.
•
Internal phase shift compensation system with obtaintion of the currents for each winding and phase, from the
line currents.
b) Monitoring and register
•
Line current (module and argument), differential current (fundamental, second and fifth harmonic) and through
RMS current measurement.
•
17 LED indicators (16 of which can be configured by the user).
•
Built in self-checking unit.
c) Analysis
•
Historical event recorder.
•
Oscillography recorder.
•
Alarm recorder.
Summary of Contents for DTP-B
Page 23: ...3 OPERATING PRINCIPLES 3 6 DTP B Digital Transformer Protection GEK 106243E ...
Page 53: ...10 INSTALLATION AND MAINTENANCE 10 2 DTP B Digital Transformer Protection GEK 106243E ...
Page 68: ...12 FIGURES GEK 106243E DTP Digital Transformer Protection 12 3 Figure 3 RS 232 Connection ...
Page 69: ...12 FIGURES 12 4 DTP B Digital Transformer Protection GEK 106243E Figure 4 Dimensions Diagram ...
Page 70: ...12 FIGURES GEK 106243E DTP Digital Transformer Protection 12 5 Figure 5 Front View ...