11. KEYBOARD AND DISPLAY
GEK-106243E
DTP Digital Transformer Protection
11-11
11.5 SINGLE KEY OPERATION
The DTP has a simplified operation mode which can be used by pressing the ENT key repeatedly. This mode
allows access to certain information about the relay without the need to remove the external methacrylate cover.
This mode can only be accessed from the standby screen. The information available in this mode is shown in
order in the following table:
MAGNITUDE
DESCRIPTION
DIFFERENTIAL Ia
Phase A differential current
DIFFERENTIAL Ib
Phase B differential current
DIFFERENTIAL Ic
Phase C differential current
DIF Ia 2ND HARM
Phase A 2
nd
harmonic current
DIF Ib 2ND HARM
Phase B 2
nd
harmonic current
DIF Ic 2ND HARM
Phase C 2
nd
harmonic current
DIF Ia 5TH HARM
Phase A 5
th
harmonic current
DIF Ib 5TH HARM
Phase B 5
th
harmonic current
DIF Ic 5TH HARM
Phase C 5
th
harmonic current
THROUGH Ia
Phase A through current
THROUGH Ib
Phase B through current
THROUGH Ic
Phase C through current
PROTECT. STATUS
Protection in / out of service
ACTIVE TABLE
Shows the active table #
DATE & TIME
Shows the unit’s date and time
Summary of Contents for DTP-B
Page 23: ...3 OPERATING PRINCIPLES 3 6 DTP B Digital Transformer Protection GEK 106243E ...
Page 53: ...10 INSTALLATION AND MAINTENANCE 10 2 DTP B Digital Transformer Protection GEK 106243E ...
Page 68: ...12 FIGURES GEK 106243E DTP Digital Transformer Protection 12 3 Figure 3 RS 232 Connection ...
Page 69: ...12 FIGURES 12 4 DTP B Digital Transformer Protection GEK 106243E Figure 4 Dimensions Diagram ...
Page 70: ...12 FIGURES GEK 106243E DTP Digital Transformer Protection 12 5 Figure 5 Front View ...