3-22
F35 Multiple Feeder Protection System
GE Multilin
3.2 WIRING
3 HARDWARE
3
3.2.7 RS232 FACEPLATE PORT
A 9-pin RS232C serial port is located on the F35 faceplate for programming with a personal computer. All that is required to
use this interface is a personal computer running the EnerVista UR Setup software provided with the relay. Cabling for the
RS232 port is shown in the following figure for both 9-pin and 25-pin connectors.
The baud rate for this port is fixed at
19200 bps
.
Figure 3–23: RS232 FACEPLATE PORT CONNECTION
3.2.8 CPU COMMUNICATION PORTS
a) OPTIONS
In addition to the faceplate RS232 port, the F35 provides two additional communication ports or a managed six-port Ether-
net switch, depending on the installed CPU module.
The CPU modules do not require a surge ground connection.
Table 3–3: CPU MODULE COMMUNICATIONS
CPU TYPE
COM1
COM2
9E
RS485
RS485
9G
10Base-F and 10Base-T
RS485
9H
Redundant 10Base-F
RS485
9J
100Base-FX
RS485
9K
Redundant 100Base-FX
RS485
9L
100Base-FX
RS485
9M
Redundant 100Base-FX
RS485
9N
10/100Base-T
RS485
9P
100Base-FX
RS485
9R
Redundant 100Base-FX
RS485
9S
Ethernet switch module with two 10/100Base-T and four 100Base-FX ports
RS485
NOTE
NOTE
Summary of Contents for F35
Page 2: ......
Page 4: ......
Page 296: ...5 174 F35 Multiple Feeder Protection System GE Multilin 5 9 TESTING 5 SETTINGS 5 ...
Page 328: ...7 8 F35 Multiple Feeder Protection System GE Multilin 7 2 TARGETS 7 COMMANDS AND TARGETS 7 ...
Page 350: ...A 16 F35 Multiple Feeder Protection System GE Multilin A 1 PARAMETER LIST APPENDIXA A ...
Page 422: ...B 72 F35 Multiple Feeder Protection System GE Multilin B 4 MEMORY MAPPING APPENDIXB B ...
Page 472: ...E 12 F35 Multiple Feeder Protection System GE Multilin E 2 DNP POINT LISTS APPENDIXE E ...