background image

Replacement installations 

Replacement installations 

For replacement installations, mount the IS-ZW-STAT-100 in place 
of the existing thermostat. You must have a “C” wire or other 24 
VAC power available at the IS-ZW-TSTAT-100 location. A new 
location will require moving your wiring. 

For replacement installations, mount the IS-ZW-STAT-100 in place 
of the existing thermostat. You must have a “C” wire or other 24 
VAC power available at the IS-ZW-TSTAT-100 location. A new 
location will require moving your wiring. 

To remove the old thermostat: 

To remove the old thermostat: 

1.  Switch off electricity to the furnace and air conditioner. 

1.  Switch off electricity to the furnace and air conditioner. 

2.  Remove the cover from the old thermostat.  

2.  Remove the cover from the old thermostat.  

Most are snap-on types and simply pull off. Some have 
locking screws on the side or front. These must be loosened.  

Most are snap-on types and simply pull off. Some have 
locking screws on the side or front. These must be loosened.  

3.  Do not remove the wires. Note the letters printed near the 

terminals. 

3.  Do not remove the wires. Note the letters printed near the 

terminals. 

4.  Attach labels (enclosed) for each wire for identification. 

4.  Attach labels (enclosed) for each wire for identification. 

Read the instructions carefully before removing any wiring 
from the existing thermostat. There is no standard color code 
for the wires. When removing wires from their terminals, 
ignore the color of the wires and label them by the terminal 
where they were connected. 

Read the instructions carefully before removing any wiring 
from the existing thermostat. There is no standard color code 
for the wires. When removing wires from their terminals, 
ignore the color of the wires and label them by the terminal 
where they were connected. 

Label the wires one at a time. You must label all of the wires 
before you proceed. This may require you to find the “other 
end” connection for each wire on your heating or air 
conditioning equipment and read the label there. See “ top 
and bottom cover sections. 

Label the wires one at a time. You must label all of the wires 
before you proceed. This may require you to find the “other 
end” connection for each wire on your heating or air 
conditioning equipment and read the label there. See “

  

Wiring” below for information on wire labels from different 
HVAC system makers.) 

Wiring” below for information on wire labels from different 
HVAC system makers.) 

5.  With all wires labeled, remove them from the old unit.  

5.  With all wires labeled, remove them from the old unit.  

Make sure the wires do not fall back inside the wall. You can 
wind them around a pencil to keep them from falling (see 
Figure 2 below). 

Make sure the wires do not fall back inside the wall. You can 
wind them around a pencil to keep them from falling (see 
Figure 2 below). 

6.  Loosen all screws on the old thermostat and remove it from 

the wall. 

6.  Loosen all screws on the old thermostat and remove it from 

the wall. 

Figure 2: Label wires 

Figure 2: Label wires 

 top 

and bottom cover sections. 

 

Note: 

A C wire or 24 VAC power is required for the IS-ZW-TSTAT-

100 to operate. If you do not have a C wire, you can run a new 
wire from the HVAC to the IS-ZW-TSTAT-100. 

The wire marked “C” will allow your thermostat to power up. If you 
do not connect or have a “C” wire, you can run a new wire from 
the HVAC to the IS-ZW-TSTAT-100. Battery power is designed for 
power loss backup and not the primary power source. If you do 
connect the C wire to the thermostat, this will extend battery life. 

See “Wiring” on page 3 for details on the different types of HVAC 
wiring your system may have. 

Prepare the wires 

Use the following guidelines for safe and secure wire connections: 

• 

You will need at least 2.6 in. of wire for each of your 
connections to the IS-AW-TSTAT-100. If you do not have 
enough wire, splice additional wire to allow enough slack. 

• 

Remove insulation 1/8 in. from the tip of each wire. 

• 

Take care not to damage the wire labels when you handle the 
wires. 

• 

Do not allow wires to touch each other or other parts on the 
thermostat.  

• 

Fan out the wires below the wall opening (see Figure 3 below) 
so that the C wire is above the C terminal, the W above the W 
terminal, etc. This allows the thermostat to fit snug to the 
wall. 

• 

Position the wires behind the thermostat and up over the 
terminal area.  Do not bunch wires behind the thermostat. 
Feed any slack back into the wall opening. 

Figure 3: Prepare wires 

From furnace

C

W

Y

RH

G

2.6 in.

 

To connect the wires: 

1.  Connect the labeled wires only to a terminal with the same 

letter label. 

2.  Insert the wire in the terminal well and tighten the screw 

securely.  

Do not over-tighten (this could cut the wire). 

To mount the thermostat to the wall: 

1.  Remove the top and bottom cover sections on the front of the 

thermostat to expose the mounting holes. 

2.  Hold the thermostat against the wall, with the wires coming 

over the top above the terminal block.  

The thermostat will cover the hole in the wall. Position the 
thermostat for best appearance. 

3.  Attach the thermostat to the wall with the screws provided. 

Mark first, and then drill a 3/16 in. (4.8 mm) hole for the insert 
at each screw location, then mount the thermostat. 

If you are mounting the thermostat to sheet rock or if you are 
using the old mounting holes, use the plastic anchors 
provided. 

4.  Replace the top and bottom cover sections. 

 

2 of 6 

 

P/N 1069534 • REV A • ISS 17MAR10 

Summary of Contents for IS-ZW-TSTAT-100

Page 1: ...sic Thermostat Temp up button Temp down button Temperature display Heat Cool mode button Fan button Gas Elec switch Reset Calibrate F C Z Wave mate Terminals Installation Caution To avoid electrical shock and to prevent damage to the furnace air conditioner and thermostat disconnect the power supply before beginning work You can do this at the circuit breaker or at the HVAC system Note Verify the ...

Page 2: ...ide the wall You can wind them around a pencil to keep them from falling see Figure 2 below Make sure the wires do not fall back inside the wall You can wind them around a pencil to keep them from falling see Figure 2 below 6 Loosen all screws on the old thermostat and remove it from the wall 6 Loosen all screws on the old thermostat and remove it from the wall Figure 2 Label wires Figure 2 Label ...

Page 3: ...nnected to the thermostat Figure 4 Two wire connections C RC Thermostat RH W Y G Heat power Heat HVACsystem W jumper wire C R To connect a three wire system C W RH or R G to the thermostat 1 Connect the R or RH wire to the RH terminal on the thermostat This connects the heater power 2 Connect the W wire to the W terminal on the thermostat This connects the heater control line 3 Connect the G wire ...

Page 4: ...eck the fan if you connected the G wire fan relay 1 Press the Fan button to On 2 Verify that air is blowing from the system 3 Return the Fan button to the Auto selection for normal operation To check heat mode 1 Press the Heat Cool Mode button to Heat 2 Press the button to raise the target temperature to 90 F Allow the system 2 minutes to respond 3 Verify that heat is blowing from the system 4 Ret...

Page 5: ...mostat make sure the wires go through both holes and tighten them down 6 If the AC fails to turn on or blow warm air then the problem is with the AC system Specifications Voltage 24 VAC supplied via the C wire Backup batteries Three AA Alkaline batteries Duracell Energizer do not use rechargeable batteries Dimensions W H D 5 5 3 5 1 5 in 140 89 38 mm Operating environment Temperature Relative humi...

Page 6: ...6 of 6 P N 1069534 REV A ISS 17MAR10 ...

Reviews: